EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
48
4. Press the
button continuously for more than 1 second for one UPS of the
system, then the system will turn to line mode.
5. Check if the difference between output voltages of the two UPS units is lower
than 0,5 V (L of the first unit with L of the second unit).
6. If the difference is higher than 0.5 V , the UPS need to be regulated.
7. Switch on the output breakers for all the UPS and then Main Output Breaker.
8. Turn on the input breakers for UPS 1, UPS2 and MAINS BREAKAER.
9. Press the
button continuously for more than 1 second for one UPS of the
system, then the system will turn to line mode.
After these steps have been completed, the unit starts its normal operation.
SWITCHING OFF THE SYSTEM
When there is a need to switch off the entire system, perform the following operations
in the given order
:
1. Press and hold the
button for more than 3 seconds for one UPS of the system.
After that, the UPS will turn into Bypass mode at once .
2. Disconnect Main O/P Breaker.
3. When completing the above action, UPS output voltage is still present. In order to
cut off the UPS output, simply cut off the utility power supply (input breaker). A
few seconds later, the ups will shut down and no output voltage is available from
the UPS output terminal.
After these operations have been completed, the shutdown process for the UPS units
will be completed (for the entire system). In order to restart the system follow the
steps in the “SYSTEM START-UP” procedure.