Installation guidelines for the POWERLINE GREEN 33 LITE UPS units in parallel/redundant operation
2016-10-27 11:56
Technical support
, tel.: +48 61 6500 400
www.ever.eu
4
The base structure must prevent collapsing under the weight of devices.
Do not cover any ventilation openings of the devices.
Leave the following service clearances around the devices:
- 0.5 m from each side if the device is not fixed to the base;
- 1.0 m from each side if the device is fixed to the base.
Ensure proper ventilation of the room where the batteries are installed (this also
applies to units with integrated batteries).
CAUTION!
Required air flow venting room
Q = 0,042 * C [m3/h] C - capacity in Ah
C)
Power supply and receiver systems
The systems shall be designed and erected only by properly licensed and
qualified personnel.
CAUTION!
The user shall ensure that the electrocution protection
system meets the applicable requirements of local laws.
CAUTION!
Do not connect the PE line to the UPS units with copper
cable tips.
The power supply and receiver lines of the UPS units shall be isolated.
It is recommended to specifically mark/label the connection outlets to distinguish
those of the isolated UPS network from the mains system outlets.
Connect the UPS units to the nearest mains switching board with copper wires in
reinforced shields (e.g. coated cables) or assure an equivalent level of
mechanical protection by applying other engineering measures (e.g. cable trays
or pipes).
CAUTION!
Only the Authorised Technical Service may connect the
device to the system and commission it. Otherwise the warranty shall be
void.