Even-GLO™ Series GA301
Page 15
October-28-15
Specifications / Details
Power & Gas Specifications
Models : GA301, GA301H & GA301T
High fire rate: Natural -
53,000 btuh
Propane -
47,000 btuh
Low fire rate: Natural -
46,000 btuh
Propane -
40,000 btuh
Gas Supply Pressure
:
Natural Gas: Minimum 6.5 ” W.C. Maximum 14.0 ” W.C.
Propane Gas: Minimum 10.8 ” W.C. Maximum 14.0 ” W.C.
Electric Supply
: 24 VAC, 0.8A
Models : GA301M & GA301MP
High fire rate: Natural -
53,000 btuh
Gas Supply Pressure
:
Natural Gas: Minimum 6.5 ” W.C. Maximum 14.0 ” W.C.
The appliance and its individual shutoff valve must be disconnected from the gas supply
piping system during any pressure testing of that system at test pressures in excess of ½
psig (3.5 kPa)
The appliance must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psig (3.5 kPa)
Installation or repair should only be done by personnel qualified for the
installation of powered gas appliances.