t12
0
999
°C/°F (2)
120
temperature above which the injection of steam generated in direct
mode is activated and below which the injection of steam generated
with external humidifier is activated (referring to the temperature
detected
by
the
environment
probe;
only
if
t0 = 2)
t13
0
999
°C/°F (2)
90
temperature above which steam reduction is activated (referring to
the temperature detected by the steam reduction probe); see also
t14
t14
1
99
°C/°F (2)
5
differential of t13
PARAM.
MIN.
MAX.
U.M.
DEF.
TEMPERATURE ALARMS
A0
1
99
°C/°F (2)
10
differential of A1
A1
0
999
°C/°F (2)
0
temperature higher than that at which the maximum temperature
alarm is activated (referring to the temperature detected by the
environment probe); see also A0 and A3
A2
0
240
min
0
maximum temperature alarm delay
A3
0
2
- - -
0
maximum temperature alarm type
0 = no alarm
1 = absolute (i.e. A1)
2
= relative to the work set-point (i.e. “work set-point + A1”)
A4
0
80/175
°C/°F (2)
70
temperature above which the temperature of use alarm is activated
(referring to the temperature of use of the control module)
0 = no alarm
PARAM.
MIN.
MAX.
U.M.
DEF.
DIGITAL INPUTS
i0
0
1
- - -
0
type of door micro switch input contact
0
= normally open (input active with closed contact)
1
= normally closed (input active with open contact)
i1
0
1
- - -
0
type of fan circuit breaker protection input contact
0
= normally open (input active with closed contact)
1
= normally closed (input active with open contact)
i2
0
1
- - -
0
fan circuit breaker protection input type
0
= for potential free contact (clamps 14 and 16)
1
= for high voltage contact (clamps 51 and 52)