EVCO S.p.A. 

 

Vcolor 338 S

 | Installer manual ver. 1.2 | Code 144VC338SE124 

page 39 of 52 

t12 

999 

°C/°F (2) 

120 

temperature above which the injection of steam generated in direct 

mode is activated and below which the injection of steam generated 

with  external  humidifier  is  activated  (referring  to  the  temperature 

detected 

by 

the 

environment 

probe; 

only 

if 

t0 = 2) 

t13 

999 

°C/°F (2) 

90 

temperature  above  which  steam  reduction  is  activated  (referring  to 

the  temperature  detected  by  the  steam  reduction  probe);  see  also 

t14 

t14 

99 

°C/°F (2) 

differential of t13 

PARAM. 

MIN. 

MAX. 

U.M. 

DEF. 

TEMPERATURE ALARMS 

A0 

99 

°C/°F (2) 

10 

differential of A1 

A1 

999 

°C/°F (2) 

temperature  higher  than  that  at  which  the  maximum  temperature 

alarm  is  activated  (referring  to  the  temperature  detected  by  the 

environment probe); see also A0 and A3 

A2 

240 

min 

maximum temperature alarm delay 

A3 

- - - 

maximum temperature alarm type 

0 = no alarm 

1 = absolute (i.e. A1) 

=  relative to the work set-point (i.e. “work set-point + A1”) 

A4 

80/175 

°C/°F (2) 

70 

temperature above which the temperature of use alarm is activated 

(referring to the temperature of use of the control module) 

0 = no alarm 

PARAM. 

MIN. 

MAX. 

U.M. 

DEF. 

DIGITAL INPUTS 

i0 

- - - 

type of door micro switch input contact 

=  normally open (input active with closed contact) 

=  normally closed (input active with open contact) 

i1 

- - - 

type of fan circuit breaker protection input contact 

=  normally open (input active with closed contact) 

=  normally closed (input active with open contact) 

i2 

- - - 

fan circuit breaker protection input type 

=  for potential free contact (clamps 14 and 16) 

=  for high voltage contact (clamps 51 and 52) 

Содержание Vcolor 338 S

Страница 1: ...144VC338SE124 page 1 of 52 Vcolor 338 S Controller for top class electric ovens for gastronomy and confectionery with TFT graphic display colour touch screen in split version and can be integrated int...

Страница 2: ...fore use of the device and follow all recommendations keep this document with the device for future consultation Only use the device in the way described in this document do not use the same as a safe...

Страница 3: ...a recipe 26 9 4 Deleting a recipe 26 10 SPECIAL CYCLES FUNCTION 27 10 1 Preliminary notes 27 10 2 Starting a special cycle 28 11 FAVOURITE CYCLES FUNCTION 29 11 1 Preliminary notes 29 11 2 Starting a...

Страница 4: ...nting with gasket 0027000007 to order separately for easy cleaning It is able to manage ventilation in on off and modulating mode in this case it is necessary to also use an external speed regulator w...

Страница 5: ...ply Vcolor 338 S 115 230 VAC Analogue inputs Vcolor 338 S environment probe J K Pt 100 2 wires needle probe J K Pt 100 2 wires steam reduction probe J K Pt 100 2 wires Digital inputs for NO NC contact...

Страница 6: ...ating mode with inversion of fan rotation direction weekly programmed switch on function programs function Notes 1 can be configured for fan left rotation or fan enabling 2 can be configured for fan r...

Страница 7: ...r interface dimensions The following drawing illustrates the device s user interface dimensions these are expressed in mm in 2 2 Installation of user interface at rear of panel The following drawing i...

Страница 8: ...rough the gasket 0027000007 to be ordered separately it is possible to guarantee the device user interface a protection rating of IP65 through the frame 0026700005 to be ordered separately it is also...

Страница 9: ...equipment containing powerful magnets large diffusers etc areas affected by direct sunlight rain humidity excessive dust mechanical vibrations or shocks any metal parts in proximity of the control mo...

Страница 10: ...al ver 1 2 Code 144VC338SE124 page 10 of 52 3 ELECTRIC CONNECTION 3 1 Electric connection The following drawing illustrates the device s electric connection Management of the ventilation in on off mod...

Страница 11: ...4 page 11 of 52 Management of the ventilation in on off mode and with single speed and inversion of the fan rotation direction parameter F0 1 Management of the ventilation in on off mode and with dual...

Страница 12: ...ution plants monitoring and surveillance systems via Web The USB communication port that allows the upload and download of the device settings through a common USB pen drive Example of connection for...

Страница 13: ...vice electric power correspond with those of the local power supply see chapter 18 TECHNICAL DATA disconnect the device power supply before proceeding with any type of maintenance position the power c...

Страница 14: ...the front parts of the device user interface parts PART MEANING 1 display The following drawing illustrates the aspect of the device s user interface rear panel The following table illustrates the mea...

Страница 15: ...tes the meaning of device s control module parts PART MEANING 1 power supply 2 digital outputs K3 and K4 3 digital output K5 4 digital output K1 5 digital output K2 6 digital inputs for potential free...

Страница 16: ...lowing table illustrates the meaning of the configuration parameters the parameters are listed with the order according to which it is appropriate that the device is configured PARAM MEANING FACTORY S...

Страница 17: ...of 52 Successively check that the remaining settings are appropriate see paragraph 14 3 List of configuration parameters 6 Connect to the electric mains 7 Switch the device on see the paragraph 7 1 S...

Страница 18: ...ion parameters see paragraph 14 2 Setting the configuration parameters 6 4 Vents The utility managed by the vent output depends on parameter u0 as follows if the parameter u0 is set at 0 the utility w...

Страница 19: ...ted by the steam reduction probe reaches the temperature established with parameter t13 and is turned back on when the temperature rises above the established with the parameter t14 i e t13 t14 only i...

Страница 20: ...re is a power cut during the cooking cycle and the duration of said interruption is lower than the time established with parameter r12 when the power supply is restored the cycle will be re proposed f...

Страница 21: ...t and the work set point is an absolute value with Delta T only if the needle probe is enabled i e if parameter P2 is set at 1 in this case the phase has duration until the temperature detected by the...

Страница 22: ...ouch 8 Repeat points 5 and 6 see also parameters r7 and r8 Operate as follows to set the humidification 9 Touch 10 Repeat points 5 and 6 Operate as follows to set the duration of the phase 11 Touch 12...

Страница 23: ...ge 23 of 52 Operate as follows to select a phase of the cooking cycle 21 Touch or Operate as follows to eliminate a phase from the cooking cycle 22 Select the phase 23 Touch for 1 s Selection of a pha...

Страница 24: ...s and the relative setting To modify the settings see the paragraph 8 2 Setting the cooking cycle Touch to open close the vent to switch the environment light on off to display the value of the proces...

Страница 25: ...thin itself It is possible to memorise up to max 99 recipes 9 2 Memorising a recipe Operate as follows to memorise a recipe 1 Set the cooking cycle see the paragraph 8 2 Setting the cooking cycle 2 To...

Страница 26: ...e is in progress 2 Touch 3 Touch 4 Touch or to select the recipe 5 Touch the middle of the display 6 Touch the middle of the display again 7 Touch the recipe will be activated 9 4 Deleting a recipe Op...

Страница 27: ...wing table illustrates the factory settings of the timed regeneration cycle SETTING DEFAULT MINIMUM MAXIMUM work set point 110 C 20 180 C humidification 70 40 100 duration of the phase 25 min 1 90 min...

Страница 28: ...a special cycle Operate as follows to start a special cycle 1 Ensure that the device is switched on and that no other procedure is in progress 2 Touch 3 Touch the identification icon of the special cy...

Страница 29: ...ph 8 2 Setting the cooking cycle in this case the last cycle performed can be started recipes from the my recipes function Special cycles function work cycles 11 2 Starting a favourite cycle Operate a...

Страница 30: ...Touch the middle of the display Operate as follows to set the switch on time 6 Touch 7 To set the time touch or within 15 s 8 To set the minutes touch the display in proximity of the centre then touc...

Страница 31: ...ess 2 Touch for 1 s Operate as follows to select a switch on 3 Touch or Operate as follows to modify a switch on 4 Repeat the 3 points 11 of the paragraph 12 2 Setting the weekly programmed switch on...

Страница 32: ...nd of the machine status Operate as follows to access the procedure 1 Ensure that the device is switched on and that no other procedure is in progress 2 Touch 3 Touch to select INTERNAL VALUES 4 Touch...

Страница 33: ...no other procedure is in progress 2 Touch 3 Touch the middle of the display Operate as follows to select a value 4 Touch Operate as follows to set a value 5 Touch or within 15 s 6 Touch Operate as fo...

Страница 34: ...ch the middle of the display 5 Touch within 15 s to set 19 6 Touch the middle of the display Operate as follows to select a parameter 7 Touch or Operate as follows to set a parameter 8 Touch the middl...

Страница 35: ...IN MAX U M DEF MAIN REGULATOR r0 1 99 C F 2 5 work set point differential referring to the temperature detected by the environment probe r1 0 r2 C F 2 0 work set point minimum referring to the tempera...

Страница 36: ...nt during cooling referring to the temperature detected by the environment probe r12 0 240 min 240 duration of a power supply cut off 3 PARAM MIN MAX U M DEF VARIOUS c0 1 120 s 10 duration of buzzer a...

Страница 37: ...regulation of the temperature during fan switch off due to the effect of the inversion of direction of rotation of the same only if F0 1 2 or 3 0 YES F4 0 F5 0 minimum fan speed intended as a percenta...

Страница 38: ...generated with an external humidifier t7 0 t6 s 30 duration of the injection of the steam generated with external humidifier corresponding to the maximum humidification t8 0 999 s 60 injection delay o...

Страница 39: ...activated referring to the temperature detected by the environment probe see also A0 and A3 A2 0 240 min 0 maximum temperature alarm delay A3 0 2 0 maximum temperature alarm type 0 no alarm 1 absolute...

Страница 40: ...2 u3 and u4 parameters will assume significance u2 0 600 ds s 10 120 duration of the inhibition of vent output from the conclusion of the brief impulse for vent opening and from the conclusion of the...

Страница 41: ...ge 41 of 52 2 the unit of measurement depends on P1 3 if the duration of the power cur is shorter that the time established with parameter r12 when the power supply is restored the cycle will be re pr...

Страница 42: ...g in a USB flash drive containing a proper text document called prog txt in the USB port of the device and wait a few seconds 3 Touch to select Upload programs 4 Touch the middle of the display the up...

Страница 43: ...perate as follows to exit the procedure before the operation is complete 6 Touch before point 4 15 5 Download of the settings contained in the configuration parameters To make the download of the sett...

Страница 44: ...es if the alarm occurs when the device is on a Delta T and a core cooking cycle cannot be allowed if the alarm occurs during a Delta T or core cooking cycle the cycle will be interrupted Steam reducti...

Страница 45: ...e cycle will be interrupted the vent will be open the technical compartment fan will be on and the remaining outputs will be off door micro switch input alarm solutions check the causes of the activat...

Страница 46: ...device USB communication port more accessible To connect the cap to the device connection cable 0810500018 or 0810500020 must be used to be ordered separately 17 3 Connection cables 0810500018 0810500...

Страница 47: ...ation 0026700005 Using the frame it is possible to aesthetically integrate the user interface when this is installed on the panel 17 6 Gasket 0027000007 According to the IEC standards using the gasket...

Страница 48: ...interface control module IP40 IP65 in the case of installation on panel with gasket 0027000007 to be ordered separately for IEC type 1 enclosure for UL and CSA IP00 Connections user interface control...

Страница 49: ...from 58 to 1 292 C Resolution 1 C 1 F Protection none thermocouple K type analogue inputs Type of sensor chromel alumel Field of measurement from 50 to 1 100 C from 58 to 2 012 C Resolution 1 C 1 F Pr...

Страница 50: ...250 VAC type SPST K4 or environment light management 1 x 8 A res output 250 VAC type SPST K5 for management of the technical compartment fan 1 x 8 A res output 250 VAC SPST type K6 for management of l...

Страница 51: ...r manual ver 1 2 PT 20 14 Code 144VC338SE124 This document is exclusive property of EVCO EVCO does not assume any liability regarding possible errors stated The customer manufacturer installer or fina...

Страница 52: ...EVCO S p A Vcolor 338 S Installer manual ver 1 2 Code 144VC338SE124 page 52 of 52 EVCO S p A Via Feltre 81 32036 Sedico Belluno ITALY Phone 39 0437 8422 Fax 39 0437 83648 info evco it www evco it...