EVCO S.p.A.
EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124
page 51 of 66
PF
Power cut alarm (HACCP alarm; in EVXV812 and EVXV815 models only).
Solutions:
-
check the device-power supply connection
-
check the value of the parameter A10.
Main consequences:
-
the device will memorise the alarm.
COH
Condenser overheated alarm.
Solutions:
-
check the temperature of the condenser
-
check the value of the parameter C6.
Main consequences:
-
the condenser fan will be switched on.
CSd
Compressor blocked alarm.
Solutions:
-
check the temperature of the condenser
-
check the value of the parameter C7
-
disconnect the device power supply and clean the condenser.
Main consequences:
-
if the error occurs during the “stand-by” status, no operating cycles can be selected or started
-
if the error occurs during an operating cycle, the cycle will be interrupted.
ESt
Configuration parameters download not completed successfully alarm.
Solutions:
-
press and release a key to restore normal display
-
download the configuration parameters again.
Main consequences:
-
the device will continue to operate normally.
CEr
Configuration parameters firmware contained in EVKEY not coinciding with that of the device.
Solutions:
-
cut the device power supply off
-
check that the configuration parameters firmware contained in EVKEY coincides with that of the
device
-
download the configuration parameters again.
Main consequences:
-
the device will continue to operate normally.
Erd
Configuration parameters upload not completed successfully alarm.
Solutions:
-
restore the factory settings
-
upload the configuration parameters again.
Main consequences:
-
the digital outputs will be switched off.