Evco S.p.A.
EVSX815 | Installer manual ver. 1.2 | Code 144XS815E124
page 37 of 58
i5
0
1
- - - -
1
effect caused by the activation of the high pressure input
0 = no
effect
1 = the compressor and the evaporator fan will be off
and the condenser fan will be on. On expiry of the
time established with parameter i7, the display will
show the flashing “
HP
” code and the buzzer will be
activated (until the input is deactivated)
i6
0
1
- - - -
0
type of high pressure input 1
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i7 -1 240
s
5
high pressure alarm signalling delay (“
HP
” code)
-1 = the alarm will not be signalled
Par.
Min.
Max.
Unit
Default
Digital outputs
u1
0
1
- - - -
0
utility managed by the output K4 (14)
0 = door heating elements (in this case, parameter u5
will assume significance)
1 = condenser fan (in this case, parameter u5 will
assume significance)
u2
0
1
- - - -
0
enabling of cabinet light switch-on/off in manual mode
during "stand-by" status (15)
1 = yes
u5 -99.0 99.0 °C/°F
(1) 20.0
cabinet temperature over which the door heating elements
are off (4)
u6 1 240 min
5
if parameter u11 is set at 1, maximum duration of needle
probe heating; see also parameter u7
if parameter u11 is set at 2, duration of UV light switch-on
for the sterilisation cycle
u7 -99.0 99.0 °C/°F
(1) 40.0
needle probe heating end temperature (temperature
detected by the needle probe); see also parameter u6