Evco S.p.A.
EVSX815 | Installer manual ver. 1.2 | Code 144XS815E124
page 36 of 58
F12 0 240
s
30
condenser fan switch-off delay from compressor switch-off
(11)
F15 0 240
s
15
evaporator fan delay from door closure, i.e. from the
deactivation of the door micro switch input
F16 -99.0 99.0 °C/°F
(1)
20.0
evaporator temperature above which the evaporator fan is
off during pre-cooling, blast chilling and deep freezing (only
if parameter F0 is set at 1); see also parameter XS8 (10)
F17 -99.0 99.0 °C/°F
(1)
90.0
cabinet temperature above which the evaporator fan is off
during pre-cooling, blast chilling and deep freezing (only if
parameter F0 is set at 1 or 2); see also parameter XS8
Par.
Min.
Max.
Unit
Default
Digital inputs
i0
0
2
- - - -
2
effect caused by opening the door, i.e. by activation of the
door micro switch (12)
0 = no
effect
1 = the compressor and the evaporator fan will be off
and the cabinet light will be on. On expiry of the
time established with parameter i2, the display will
show the flashing “
id
” code and the buzzer will be
activated (until the door is closed); see also
parameter F15 (13)
2 = the evaporator fan will be off and the cabinet light
will be on. On expiry of the time established with
parameter i2, the display will show the flashing “
id
”
code and the buzzer will be activated (until the door
is closed); see also parameter F15
i1
0
1
- - - -
0
type of door micro switch input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i2 -1 120 min
5
door open alarm signalling delay (“
id
” code)
-1 = the alarm will not be signalled