background image

114J500E4.01 - 04/2021

EVJ 500 series

Temperature/humidity and food processing controllers

WARNING

Read and fully understand 
user manual before using 
this device.

Failure to follow these
instructions can reslut in
death, serious injury.

Содержание EVJ 500 Series

Страница 1: ...2021 EVJ 500 series Temperature humidity and food processing controllers WARNING Read and fully understand user manual before using this device Failure to follow these instructions can reslut in death...

Страница 2: ...installation and the environment 14 3 3 Dimensions 15 3 4 Installation 15 3 4 1 Minimum distances 16 4 ELECTRICAL CONNECTIONS 17 4 1 WIRING BEST PRACTICES 17 4 1 1 Wiring guidelines 17 4 1 2 Fixed scr...

Страница 3: ...Operation 32 7 2 HEATING COOLING TEMPERATURE IN THE NEUTRAL ZONE 32 7 2 1 Operation 32 7 3 TEMPERATURE AND DEHUMIDIFICATION WITH THE COMPRESSOR 33 7 3 1 Operation 33 7 3 2 Temperature priority over de...

Страница 4: ...COPYING THE PARAMETERS 40 8 3 1 Introduction 40 8 3 2 Uploading the parameters from the controller to EVJKEY 40 8 3 3 Downloading the parameters from EVJKEY to the controller 40 9 PARAMETERS 41 9 1 TA...

Страница 5: ...ddition to carrying out a product evaluation and test in relation to its specific application or use Users can send us comments and suggestions on how to improve or correct this publication Neither EV...

Страница 6: ...t in death or serious injury CAUTION CAUTION indicates a potentially hazardous situation which if not avoided could cause minor or moderate injury NOTICE NOTICE indicates a situation not related to ph...

Страница 7: ...uding applications that generate or could potentially generate hazardous atmospheres Only install this device in areas and for applications which are reliably free from hazardous atmospheres DANGER RI...

Страница 8: ...ures of the EVJ 500 series are 2 analogue inputs of which 1 analogue input for temperature 1 analogue input for humidity 2 voltage free digital inputs of which 1 digital input configurable as an analo...

Страница 9: ...0 series 04 2021 9 Type P n Description EVIF25TWX Wi Fi module EVIF22TSX Module for TTL RS 485 serial interface EVIF23TSX Module for TTL RS 485 serial interface with built in clock EVJKEY Programming...

Страница 10: ...ltage 4000 V Power supply 12 Vac dc 10 50 60 Hz Consumption 10 VA maximum Ambient operating conditions 0 55 C 32 131 F 10 90 RH non condensing Transportation and storage conditions 25 70 C 13 158 F 10...

Страница 11: ...nput features Default NTC 10 k at 25 C BETA 3435 PTC KTY 81 121 990 at 25 C RH EVHTP5 0 Digital input Pb1 Temperature probe Pb2 Humidity probe EVHTP5 0 Pb3 If Pr3 5 Evaporator probe Range 50 120 C 58...

Страница 12: ...tures Default NTC 10 k at 25 C BETA 3435 PTC KTY 81 121 990 at 25 C RH EVHTP5 0 Digital input Pb1 Temperature probe Pb2 Humidity probe EVHTP5 0 Pb3 If Pr3 5 Evaporator probe Range 50 120 C 58 248 F 50...

Страница 13: ...tures Default NTC 10 k at 25 C BETA 3435 PTC KTY 81 121 990 at 25 C RH EVHTP520 Digital input Pb1 Temperature probe Pb2 Humidity probe EVHTP520 Pb3 If Pr3 5 Evaporator probe Range 50 120 C 58 248 F 50...

Страница 14: ...ON INSTALLATION AND THE ENVIRONMENT Before carrying out any work on the equipment read these instructions carefully making sure you understand everything DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR EL...

Страница 15: ...the wiring connections Use the required safety interlocks where personnel and or equipment hazards exist Install and operate this equipment in a cabinet appropriately rated for its intended environmen...

Страница 16: ...114J500E4 01 EVJ 500 series 04 2021 16 3 4 1 Minimum distances 40 1 57 40 1 57 mm in 40 1 57 40 1 57 Fig 3 EVJ 500 series minimum installation distances...

Страница 17: ...se connections electromagnetic interference could cause the signal to deteriorate Deteriorated signals can lead to unpredictable operation of the controller or modules and connected equipment WARNING...

Страница 18: ...supply 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Pr3 0 N C TTL Out1 Out2 Out3 Out4 Out5 Out6 1 2 3 4 5 6 Pb1 Pb2 ID1 Pb3 Power supply 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Pr3 0 N C TTL Out1...

Страница 19: ...ction Access the setpoint menu 5 3 ICONS Icon ON Flashing OFF Cooling request Dehumidification request Protection delay ON Compressor OFF Defrost active Defrost delay ON Dripping ON Evaporator fans ON...

Страница 20: ...CONTROLLER OPERATION 5 4 1 Switching the controller ON OFF To switch the controller on off press the key for at least 3 seconds 17 5 60 OverTemp c OverTemp Fig 7 Main screen Fig 8 Controller switching...

Страница 21: ...the EVJ 500 series can be activated by touching the key Sanitation this activates the sanitation function EVJ 526 only Defrost this activates defrost if all the conditions are met see 6 DEFROST on pag...

Страница 22: ...the setpoint To change the setpoint 17 5 60 OverTemp Door open c Setpoint 1 1 2 3 4 2 20 0 0 50 C Timer 1 9 55 hh mm 5 Timer 1 5 1 5 2 2 9 55 hh mm Setpoint 2 1 2 0 10 95 Fig 11 Changing the setpoint...

Страница 23: ...cycle is stopped on page 23 17 5 60 OverTemp Program 01 Stop c Fig 12 Display when cycle is stopped 5 4 7 Setting the clock To set the clock date and time on the device 17 5 60 OverTemp Door open c 3...

Страница 24: ...Air control Air interval Air time Language Menu Service 1 1 2 3 4 5 6 2 Internal Values Alarms Data Memory Reset Parameters Restore Haccp Menu Parameters Internal Values Alarms Data Memory Reset Para...

Страница 25: ...you can choose from the following options to set the air change mode 0 Activated in all 3 processes default 1 Activated in processes 1 dripping and 2 drying 2 Activated in processes 2 drying and 3 agi...

Страница 26: ...ore hot gas defrost min 0 99 Defrost starts up when the time set by d0 has elapsed in the mode set by d1 Defrost duration is determined by d3 while the temperature threshold to end defrost is determin...

Страница 27: ...ways Par Description MU Range d1 Type of defrost 0 Electrical heaters 1 Cycle reversed hot gas 2 When compressor stops 0 3 6 3 1 Defrost with electrical heaters Defrost with electrical heaters is obt...

Страница 28: ...request ON OFF d2 ON OFF d3 d7 End of defrost Fig 16 Defrost with electrical heaters End of defrost due to temperature Pb3 ON OFF d2 ON OFF d3 d7 Defrost request End of defrost Fig 17 Defrost with ele...

Страница 29: ...hed Temperature to end defrost set by parameter d2 must be reached The defrost configuration parameters with cycle reversed are Par Description MU Range C0 Compressor ON delay from power on min 0 240...

Страница 30: ...114J500E4 01 EVJ 500 series 04 2021 30 Pb3 ON OFF d2 ON OFF d3 d7 d15 Defrost request End of defrost Fig 19 Defrost with cycle reversed End of defrost due to maximum time...

Страница 31: ...th cycle reversed are Par Description MU Range d0 Defrost interval h 0 99 d1 Type of defrost 0 Electrical heaters 1 Cycle reversed hot gas 2 When compressor stops 0 3 d3 Defrost duration min 0 99 d7 E...

Страница 32: ...er receives a heating request Heating output Heaters between setpoint 1 and setpoint 1 R12 When the temperature read by Pb1 reaches the value of setpoint 1 R12 the controller activates the heater outp...

Страница 33: ...tputs is activated 7 3 2 Temperature priority over dehumidification If rd4 1 2 the dehumidification function is activated and works with the compressor and heater outputs This makes it necessary to se...

Страница 34: ...ping Conditions for activation The compressor is activated if the following conditions are met The controller is on regulation is blocked when the controller is in stand by Probe Pb1 is working Compre...

Страница 35: ...rom compressor 1 switch on s 0 240 7 6 1 Operating diagrams Normal compressor operation Pb1 ON OFF Setpoint 1 Setpoint 1 r0 C0 C2 C3 C3 Compressor request Compressor OFF Fig 25 Normal compressor opera...

Страница 36: ...r manages two compressors Activating compressor 2 Compressor 2 is activated after a delay C11 from compressor 1 switch off If active compressor 2 uses the Setpoints Differentials Delays and Protection...

Страница 37: ...te according to parameter F0 Par Description MU Range F0 Evaporator fan mode in normal operating mode With F0 0 it is possible to manage cycles by setting F11 F12 rd2 rd3 rh2 rh3 0 In cycles 1 Always...

Страница 38: ...the temperature Pb3 goes above the alarm threshold C6 7 10 ENERGY SAVING 7 10 1 Operation Energy saving can be activated By digital input iC1 1 By key see 5 4 4 Functions that can be activated by key...

Страница 39: ...Sanitation in stand by 0 UV lamps 1 Ozone generator in stand by temperature humidity regulation off 2 Ozone generator in stand by and operating temperature humidity regulation suspended 0 2 8 2 AGING...

Страница 40: ...lly uploaded This may take a couple of seconds If the upload is successful the OK LED stays on while the ERROR LED goes off If it has not been successful the OK LED goes off while the ERROR LED stays...

Страница 41: ...ature measurement unit if the value is changed the temperature parameter limits must be reset manually 0 C 1 F 0 1 0 0 0 2 Pr3 Probe Pb3 configuration 0 Digital input ID3 1 Condenser probe 2 Needle pr...

Страница 42: ...th compressor and heating 0 Disabled 1 Compressor 2 Compressor and heating 0 3 1 1 1 2 rd5 Heat and dehumidification with defrost output 0 No 1 Yes 0 1 0 0 0 2 rh0 Humidification differential 25 1 3 3...

Страница 43: ...ter door closed min 0 240 15 15 15 2 A10 Duration of power failure to record alarm min 0 240 15 15 15 2 A11 Hysteresis referring to A1 and A4 to determine alarm reset threshold C F 0 1 15 1 0 1 0 1 0...

Страница 44: ...events are counted for manual reset min 0 120 60 60 60 2 i8 Digital input event counting for pressure switch and or thermal switch alarm 0 Always automatic 1 Always manual 0 15 1 1 1 2 AUXILIARY OUTPU...

Страница 45: ...0 16 11 11 11 2 uc6 Configure relay output out6 Same as uc1 0 16 12 12 12 2 KEY CONFIGURATION Group POF Enable stand by key ON OFF 0 Disabled 1 Enabled 0 1 1 1 1 2 PLi Enable light key in stand by 0...

Страница 46: ...Disabled h 0 23 2 Hd3 Defrost 3 activation time Disabled h 0 23 2 Hd4 Defrost 4 activation time Disabled h 0 23 2 Hd5 Defrost 5 activation time Disabled h 0 23 2 Hd6 Defrost 6 activation time Disabled...

Страница 47: ...mperature read by Pb2 goes above the alarm threshold AH4 2 id Door open alarm Digital input activated for a time i2 Code id displayed Regulators blocked depending on the current function in iC1 7 8 or...

Страница 48: ...operty Rights Code CPI EVCO forbids the reproduction and distribution even in part of the contents unless express authorisation is obtained directly from EVCO The customer manufacturer installer or en...