Evco S.p.A. • Code 104F214E00 • page 4/8

PT • 45/10

• the compressor blocked due to condenser temperature

alarm (“

CSd

” code) will never be activated

• the alarm output will be activated (only if parameter u1

is set at 3)

• if parameter u1 is set at 6, the condenser fan will function

in parallel to the compressor

rtc

Clock error
Solutions:
• set the day and real time again
Main consequences:
• if parameter d8 is set at 4, the instrument will function as

if parameter is set at 0

• the HACCP function will not supply information relative

to the date and time the alarm occurred

• the Energy Saving function will not be available in real

time

• the alarm output will be activated (only if parameter u1

is set at 3)

ErC

Error of compatibility user interface-control module
Solutions:
• check the compatibility user interface-control module

(check the data related in the labels)

Main consequences:
• the control module will keep working correctly

ErL

Error of communication user interface-control module
Solutions:
• check the connection user interface-control module
Main consequences:
• the control module will keep working correctly

When the cause of the alarm disappears, the instrument restores normal
functioning, except for the clock error (“

rtc

” code) that requires setting

of the day and real time.

11

TECHNICAL DATA

11.1

Technical data

User interface container:

 open frame board behind a methacrylate

sheet.

Control module container: 

open frame board.

User interface protection rating (front):

 IP 65.

Control module protection rating:

 IP 00.

User interface connections:

 screw terminal board (at the control

module).
The user interface connects to the control module via a 4-way cable:
the maximum length allowed for the connection cable is 20 m
(65.614 ft; the cable is not supplied with the instrument).

Control module connections:

 6.3 mm faston (0.248 in, power

supply and outputs), screw terminal board (to the user interface and
inputs), 6-pole connector (serial port).

Temperature of use:

 from 0 to 55 

°

C (from 32 to 131 

°

F, 10 ... 90%

relative humidity without condensate).

User interface power supply:

 the user interface is powered by the

control module.

Control module power supply:

 115 ... 230 VCA, 50/60 Hz, 10 VA.

Maintaining the clock data in a power cut:

 24 h with battery

charged.

Battery charging time:

 2 min without interruptions (the battery is

charged by the instrument power supply).

Alarm buzzer:

 incorporated (in the user interface).

Measurement inputs:

 3 (cabinet probe, evaporator probe and

condenser probe) for NTC probes

Digital inputs:

 2 (door micro switch and multipurpose) for normally

open/normally closed contact (potential free contact, 5 V 1 mA).

Range of measurement:

 from -40 to 105 

°

C (from 40 to 220 

°

F).

Resolution:

 0.1 

°

C/1 

°

C/1 

°

F.

Digital outputs:

 4 relays:

compressor relay:

 30 A res. @ 250 VCA (NO

contact)

defrosting relay:

 16 A res. @ 250 VCA (contact

in exchange)

evaporator fan relay:

 8 A res. @ 250 VCA (NO

contact)

fourth output relay:

 16 A res. @ 250 VCA (NO

contact).

The maximum current allowed on the loads is 20 A.
Serial port:

 port for communication with the Parameters Manager

set-up software system or to the monitoring and supervision system of
RICS plants (via TTL, with MODBUS communication protocol) or with
the EVKEY programming key.

Содержание EVF214

Страница 1: ...Preliminary considerations The following functioning states exist the on status the instrument is powered and on the regulators can be on the stand by status the instrument is powered but is switched...

Страница 2: ...lay will show dd followed by the two numbers of the day press and release the key or the key within 15 s To modify the time press and release the key during modification of the day of the month the di...

Страница 3: ...he evaporator probe see parameters d2 d3 and d11 press a key to restore normal display Main consequences the instrument continues to function regularly When the cause of the alarm has disappeared the...

Страница 4: ...tection rating IP 00 User interface connections screw terminal board at the control module The user interface connects to the control module via a 4 way cable the maximum length allowed for the connec...

Страница 5: ...nce request is signalled 0 no function DEFROSTING if d8 0 1 or 2 defrosting interval 8 0 defrosting at intervals will never be activated if d8 3 maximum defrosting interval type of defrosting 0 ELECTR...