Evco S.p.A. • Code 104F214E00 • page 3/8

Alternatively:
• exit the succession of information
• press and release the   key.
If the instrument has no alarm in the memory, the “

LS

” label will not

be displayed.

6.3

Deletion of the list of HACCP alarms

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the   key down for 1 s: the display will show the first label

available

• press and release the   key or the   key to select “

rLS

• press and release the   key
• press and release the   key or the   key within 15 s. to set “

149

• press and release the   key or do not operate for 15 s the display

will show flashing “

- - - -

” for 4 s. and the HACCP LED will switch-off,

after which the instrument will exit the procedure.

If the instrument has no alarm in the memory, the “

rLS

” label will not

be displayed.

7

COUNTING THE COMPRESSOR FUNCTIONING
HOURS

7.1

Preliminary considerations

The instrument can memorise up to 9.999 compressor functioning
hours, after which the number “

9999

” flashes.

7.2

Display of the compressor functioning hours

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the   key down for 1 s: the display will show the first label

available

• press and release the   key or the   key to select “

CH

• press and release the   key.
To exit the procedure:
• press and release the   key or do not operate for 60 s
• press and release the   key or the   key until the display shows the

cabinet temperature or do not operate for 60 s.

Alternatively:
• press and release the   key.

7.3

Deletion of the compressor functioning hours

• make sure that the keyboard is not locked and that no procedure is

in progress

• hold the   key down for 1 s: the display will show the first label

available

• press and release the   key or the   key to select “

rCH

• press and release the   key
• press and release the   key or the   key within 15 s. to set “

149

• press and release the   key or do not operate for 15 s the display

will show flashing “

- - - -

” for 4 s, after which the instrument will exit

the procedure.

8

SIGNALS AND INDICATIONS

8.1

Signals

LED

MEANING
compressor LED
if on, the compressor will be on
if flashing:
• the work set-point modification will be in progress (with

the procedure indicated in paragraph 5.2)

• a compressor protection will be in progress:
- parameters C0, C1, C2
- parameter i7
defrosting LED
if it is on:
• defrosting will be in progress
• pre-dripping will be in progress
- parameter d16
if flashing:
• defrosting will be requested but a compressor protection

will be in progress:

- parameters C0, C1 and C2
• dripping will be in progress:
- parameter d7
• refrigerant fluid heating will be in progress:
- parameter d15
evaporator fan LED
if on, the evaporator fan will be on
if it flashes, the evaporator fan standstill is in progress
- parameter F3
cabinet light LED
if on, the cabinet light will have been switched-on in
manual mode (only if parameter u1 is set at 0)
if flashing, the cabinet light will have been switched on in
remote mode:
- parameter i0 (only if parameter u1 is set at 0)
multipurpose LED
if it is on:
• the demisting heaters will be on (only if parameter u1 is

set at 1)

• the auxiliary output will have been switched-on in manual

mode (only if parameter u1 is set at 2)

• the door heaters will be on (only if parameter u1 is set at 4)
• the evaporator valve will be activated (only if parameter

u1 is set at 5)

• the condenser fan will be on (only if parameter u1 is set at 6)
if flashing:
• the auxiliary output will have been switched-on in remote

mode:

• see parameters i5 and i6
Main consequences:
• the effect established with parameter i5
• the alarm output will be activated (only if parameter u1

is set at 3)

iSd

Pressure switch alarm
Solutions:
• check the causes that brought about the activation of the

input

• see parameters i5, i6, i7, i8 and i9
• switch the instrument off and back on again or cut the

power supply off

Main consequences:
• the regulators will be switched off
• the alarm output will be activated (only if parameter u1

is set at 3)

COH

Overheated condenser alarm
Solutions:
• verify the temperature of the condenser
• see parameter C6
Main consequences:
• the alarm output will be activated (only if parameter u1

is set at 3)

• if parameter u1 is set at 6, the condenser fan will be on

CSd

Blocked compressor alarm
Solutions:
• verify the temperature of the condenser
• see parameter C7
• switch the instrument off and back on again: when the

instrument is switched back on, if the condenser
temperature is still above that established with parameter
C7, the power supply must be disconnected and the
condenser cleaned.

Main consequences:
• the evaporator compressor and fan will be switched off
• the alarm output will be activated (only if parameter u1

is set at 3)

dFd

Defrosting concluded due to maximum duration alarm
Solutions:
• check the integrity of the evaporator probe
• see parameters d2, d3 and d11
• press a key to restore normal display
Main consequences:
• the instrument continues to function regularly

When the cause of the alarm has disappeared, the instrument will go
back to normal functioning, except for the following alarms:
• the power supply cut-off alarm (“

PF

” code), which requires a key to

be pressed

• the pressure switch alarm (“

iSd

” code), which requires the instrument

to be switched off or the power supply to be cut-off

• the compressor blocked due to condenser temperature alarm (“

CSd

code), which requires the instrument to be switched off or the power
supply to be cut-off

• the defrosting concluded due to maximum duration alarm (“

dFd

code), which requires a key to be pressed.

10

ERRORS

10.1

Errors

CODE MEANING

Pr1

Cabinet probe error
Solutions:
• check that the probe is the NTC type
• check the integrity of the probe
• check the instrument-probe connection
• verify the temperature of the cabinet
Main consequences:
• the activity of the compressor will depend on parameters

C4 and C5

• defrosting will never be activated
• the alarm output will be activated (only if parameter u1

is set at 3)

• the door heaters will be switched-off (only if parameter u1

is set at 4)

• the evaporator valve will be deactivated (only if

parameter u1 is set at 5)

Pr2

Evaporator probe error
Solutions:
• the same as the previous case but relative to the evaporator

probe

Main consequences:
• if parameter P3 is set at 1, defrosting will last for the time

established with parameter d3

• if parameter P3 is set at 1 and parameter d8 is set at 2 or 3,

the instrument will function as if parameter d8 is set at 0

• if parameter F0 is set at 3 or 4, the instrument will function

as if parameter is set at 2

• the alarm output will be activated (only if parameter u1

is set at 3)

Pr3

Condenser probe error
Solutions:
• the same as the previous case but relative to the condenser

probe

Main consequences:
• the overheated condenser alarm (“

COH

” code) will

never be activated

- parameter i5 (only if parameter u1 is set at 2)
• the condenser fan switch-off delay will be in progress:
- parameter F12 (only if parameter u1 is set at 6)
clock LED
if it flashes, modification of the day and real time will be in
progress

HACCP

HACCP LED
id it is on, all of the information regarding the HACCP alarms
has not been displayed
if it flashes, the instrument will have memorised at least one
new HACCP alarm
if it is off, all of the information regarding the HACCP alarms
will have been displayed or the list of HACCP alarms will
have been deleted
Energy Saving LED
if on, the Energy Saving function will be in progress:
- parameters r4, F13, F14, i5, i10, HE1 and HE2
maintenance LED
if on, compressor maintenance will be requested:
- parameter C10
Overcooling LED
if on, the Overcooling function will be in progress
- parameters r5 and r6
alarm LED
if it is on, an alarm or an error is in progress

°

C

degree Celsius LED
if it is on, the unit of measurement of the temperatures will
be the degree Celsius:
- parameter P2

°

F

degree Fahrenheit LED
if it is on, the unit of measurement of the temperatures will
be the degree Fahrenheit:
- parameter P2
on/stand-by LED
if it is on, the instrument is in the stand-by status

8.2

Indications

CODE MEANING

rhL

functioning due to low relative humidity percentage is in
progress

rhH

functioning due to high relative humidity percentage is in
progress

Loc

the keyboard is locked:
- see paragraph 4.13
the work set-point is blocked:
- parameter r3

- - - -

the functioning requested is not available

9

ALARMS

9.1

Alarms

CODE MEANING

AL

Minimum temperature alarm (

HACCP alarm

)

Solutions:
• check the temperature associated to the alarm
• see:
- see parameters A0, A1 and A2
Main consequences:
• if parameter A0 is seta at 0, the instrument memorises the

alarm

• the alarm output will be activated (only if parameter u1

is set at 3)

AH

Maximum temperature alarm (

HACCP alarm

)

Solutions:
• verify the temperature of the cabinet
• see:
- parameters A4 and A5
Main consequences:
• the instrument memorises the alarm
• the alarm output will be activated (only if parameter u1

is set at 3)

id

Door micro switch input alarm (

HACCP alarm

)

Solutions:
• check the causes that brought about the activation of the

input

• see parameters i0, i1 and i4
Main consequences:
• the effect established with parameter i0
• if parameter i4 is set at 1, the instrument memorises the

alarm, on condition that parameter i2 is not set at -1

• the alarm output will be activated (only if parameter u1

is set at 3)

PF

Power apply cut-off alarm (

HACCP alarm

)

Solutions:
• check the causes of the power cut
• see parameters A10 and A12
• press a key to restore normal display
Main consequences:
• if the duration of the power supply cut-off is longer than

the time established with parameter A10, the instrument
will memorise the alarm

• the alarm output will be activated (only if parameter u1

is set at 3)

iA

Multipurpose input alarm
Solutions:
• check the causes that brought about the activation of the

input

Содержание EVF214

Страница 1: ...Preliminary considerations The following functioning states exist the on status the instrument is powered and on the regulators can be on the stand by status the instrument is powered but is switched...

Страница 2: ...lay will show dd followed by the two numbers of the day press and release the key or the key within 15 s To modify the time press and release the key during modification of the day of the month the di...

Страница 3: ...he evaporator probe see parameters d2 d3 and d11 press a key to restore normal display Main consequences the instrument continues to function regularly When the cause of the alarm has disappeared the...

Страница 4: ...tection rating IP 00 User interface connections screw terminal board at the control module The user interface connects to the control module via a 4 way cable the maximum length allowed for the connec...

Страница 5: ...nce request is signalled 0 no function DEFROSTING if d8 0 1 or 2 defrosting interval 8 0 defrosting at intervals will never be activated if d8 3 maximum defrosting interval type of defrosting 0 ELECTR...

Страница 6: ...ctivity during normal functioning 0 off 1 on se also F13 F14 and i10 2 parallel to the compressor se also F9 F13 F14 and i10 3 depending on F1 16 4 off if the compressor is off depending on F1 if the...

Страница 7: ...so that the alarms contactor is reset only if i5 4 time that must pass without activation of the door micro switch input after the cabinet temperature has reached the work set point so that the Energy...

Страница 8: ...ut If the input is activated during defrosting or standstill of the evaporator fan the activation will not have any effect on the compressor 20 the instrument memorises the alarm on expiry of the time...

Отзывы: