EVCO S.p.A. | EV3221 & EV3231 | Instruction sheet ver. 1.0 | Code 1043221E103 | Page 1 of 2 | PT 44/16 

EV3221 & EV3231 

Controllers for refrigerated cabinets, undercounters and islands, 

with energy-saving strategies 

 

 

 

 

ENGLISH 

Controllers for normal temperature units. 

Power supply 230 VAC, 115 VAC or 12-24 VAC/DC (according to the model). 

Incorporated clock (according to the model). 

Cabinet probe (PTC/NTC). 

Door switch/multi-purpose input. 

Compressor  relay  16  A  res.  @  250  VAC  or  30  A  res.  @  250  VAC  (according  to  the 

model). 

Alarm buzzer. 

TTL or RS-485 MODBUS slave port for BMS (according to the model). 

Cooling or heating operation. 

 

MEASUREMENTS AND INSTALLATION 

Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided. 

 

 

 

INSTALLATION PRECAUTIONS 

The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in) 

Ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS section. 

Do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks. 

In compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them. 

 

ELECTRICAL CONNECTION 

 

 

N.B. 

Use cables of an adequate section for the current running through them. 

To reduce any electromagnetic interference connect the power cables as far away 

as possible from the signal cables. 

 

 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

If using an electrical or pneumatic screwdriver, adjust the tightening torque. 

If  the  device  has  been  moved  from  a  cold  to  a  warm  place,  the  humidity  may  have 

caused  condensation  to  form  inside.  Wait  about  an  hour  before  switching  on  the 

power. 

Make  sure  that  the  supply  voltage,  electrical  frequency  and  power  are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS.

 

Disconnect the power supply before doing any type of maintenance. 

Do not use the device as safety device. 

For repairs and for further information, contact the EVCO sales network. 

 

FIRST-TIME 

1. 

Install  following  the  instructions  given  in  the  section  MEASUREMENTS AND INSTALLA-

TION

2. 

Power up the device as shown in the section ELECTRICAL CONNECTION and an internal 

test will be run. 

 

The test normally takes a few seconds, when it is finished the display will switch off. 

3. 

Configure the device as shown in the section Setting configuration parameters

 

Recommended configuration parameters for first-time use. 

PAR. 

DEF. 

PARAMETER 

MIN... MAX. 

SP 

0.0 

setpoint 

r1... r2 

P0 

probe type 

0  = PTC 

1  = NTC 

P2 

temperature unit of measurement 

0  = °C 

1  = °F 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section  CONFIGURA-

TION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-

out powering up the device. 

6. 

For  the  connection  in  an  RS-485  network  connect  the  interface  EVIF22TSX  or 

EVIF23TSX,  to  activate  real  time  functions  connect  the  module  EVIF23TSX  (or  use 

EV3... XRS); see the relevant instruction sheets. 

7. 

Power up the device. 

 

USER INTERFACE AND MAIN FUNCTIONS 

 

 

 

4.1 

Switching the device on/off 

1. 

 

If POF = 1, touch the ON/STAND-BY key for 4 s. 

If the device is switched on, the display will show the P5 value ("cabinet temperature" default); 

if the display shows an alarm code, see the section ALARMS

LED 

ON 

OFF 

FLASHING 

 

compressor on 

 

compressor off 

 

-  compressor protection active 

-  setpoint setting active 

 

defrost active 

 

 

dripping active 

 

HACCP 

saved HACCP alarm 

 

 

new HACCP alarm saved 

 

 

energy saving active 

 

 

 

 

request  for  compres-

sor service 

 

 

 

-  settings active 

-  access  to  additional  functions 

active 

°C/°F 

view temperature 

 

 

overcooling or overheating active 

 

 

device off 

 

device on 

 

device on/off active 

 

 

If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and 

the keypad will lock automatically. 

 

4.2 

Unlock keypad 

Touch a key for 1 s: the display will show the label “UnL”. 

 

4.3 

Set the setpoint 

Check that the keypad is not locked. 

1. 

 

Touch the SET key. 

2. 

 

Touch  the  UP  or  DOWN  key  within  15  s  to  set  the  value  within 

the limits r1 and r2 (default “-50... 50”) 

3. 

 

Touch the SET key (or do not operate for 15 s). 

 

4.4 

Activate manual defrost (if r5 = 0, default) 

Check that the keypad is not locked and that overcooling is not active. 

1. 

 

Touch the UP key for 2 s. 

If P4 = 1, defrost is activated provided that the evaporator temperature is lower than the d2 

threshold. 

 

4.5 

Silence buzzer (if A13 = 1) 

Touch a key. 

 

ADDITIONAL FUNCTIONS 

5.1 

Activate/deactivate overcooling, overheating and manual energy saving 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key. 

 

FUNCTION 

CONDITION 

CONSEQUENCE 

overcooling 

 

r5  =  0,  r8  =  1  and  defrost 

not active 

the  setpoint  becomes  “setpoint  - 

r6”, for the r7 duration 

overheating 

 

r5 and r8 = 1 

 

the  setpoint  becomes  “setpoint  + 

r6”, for the r7 duration 

energy saving 

 

r5 = 0 and r8 = 2 

 

the  setpoint  becomes  “setpoint  + 

r4”, at maximum for HE2 duration 

 

5.2 

View/delete HACCP alarm information 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select a label. 

 

LAB. 

DESCRIPTION 

 

LS 

view HACCP alarm information

 

 

rLS 

delete HACCP alarm information

 

3. 

 

Touch the SET key. 

4. 

 

Touch the UP or DOWN key to select an alarm code (when label 

LS” is selected) or to set “149” (when label “rLS” is selected). 

 

COD.  DESCRIPTION 

 

AL 

low temperature alarm 

 

AH 

high temperature alarm 

 

id 

door switch alarm 

 

PF 

 

power  failure alarm  (available  in  EV3...  XRS  or  if  module EVIF23TSX  is  con-

nected) 

5. 

 

Touch the SET key. 

6. 

 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

 

Example of alarm information (e.g. a high temperature alarm). 

 

8.0 

 

 

critical  value  (cabinet/  calculated  product  temperature) 

was 8.0 °C/°F 

 

 

Sta 

(available in EV3... XRS or if module EVIF23TSX is connected) 

 

 

 

y15 

alarm signalled in 2015

 

 

 

 

n03 

alarm signalled in March

 

 

 

 

d26 

alarm signalled on 26 March 2015

 

 

 

 

h16 

alarm signalled at 16:00

 

 

 

 

n30 

alarm signalled at 16:30

 

 

 

dur 

 

 

 

 

 

h01 

alarm lasted 1h

 

 

 

 

n15 

alarm lasted 1h 15 min

 

 

 

5.3 

View/delete  compressor  functioning  hours  and  view  compressor  start-up 

number 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select a label. 

 

LAB. 

DESCRIPTION 

 

CH 

view compressor functioning hours (hundreds) 

 

rCH 

delete compressor functioning hours 

 

nS1 

compressor start-up number (thousands) 

3. 

 

Touch the SET key. 

4. 

 

Touch the UP or DOWN key to set “149” (when label “rCH” is se-

lected). 

5. 

 

Touch the SET key. 

6. 

 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

 

5.4 

View the temperature detected by the probes 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select a label. 

 

LAB. 

DESCRIPTION 

 

Pb1 

cabinet temperature

 

 

Pb2 

auxiliary temperature (if P4 = 1 or 2)

 

3. 

 

Touch the SET key. 

4. 

 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

 

5.5 

View the project number and the firmware revision 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select a label. 

 

LAB. 

DESCRIPTION 

 

PrJ 

view the project number

 

 

rEU 

view the firmware revison

 

3. 

 

Touch the SET key. 

4. 

 

Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 

the procedure. 

 

SETTINGS 

6.1 

Setting configuration parameters 

1. 

 

Touch the SET key for 4 s: the display will show the label “PA”. 

2. 

 

Touch the SET key. 

3. 

 

Touch the UP or DOWN key within 15 s to set the PAS value (de-

fault “-19”). 

4. 

 

Touch the SET key (or do not operate for 15 s): the display will 

show the label “SP”. 

5. 

 

Touch the UP or DOWN key to select a parameter. 

6. 

 

Touch the SET key. 

7. 

 

Touch the UP or DOWN key within 15 s to set the value. 

8. 

 

Touch the SET key (or do not operate for 15 s). 

9. 

 

Touch the SET key for 4 s (or do not operate for 60 s) to exit the 

procedure. 

 

6.2 

Set  the  date,  time  and  day  of  the  week  (available  in  EV3...  XRS  or  if  module 

EVIF23TSX is connected) 

 

 

N.B. 

Do not disconnect the device from the mains within two minutes since the setting of 

the time and day of the week. 

 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select the label “rtc”. 

3. 

 

Touch the SET key: the display will show the label “yy” followed 

by the last two figures of the year. 

4. 

 

Touch the UP or DOWN key within 15 s to set the year. 

5. 

Repeat actions 3. and 4. to set the next labels. 

 

LAB. 

DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL 

 

month (01… 12) 

 

day (01… 31) 

 

time (00… 23) 

 

minute (00… 59) 

6. 

 

Touch the SET key: the display will show the label for the day of 

the week. 

7. 

 

Touch  the  UP  or  DOWN  key  within  15  s  to  set  the  day  of  the 

week.

 

 

LAB. 

DESCRIPTION 

 

Mon 

Monday 

 

tuE 

Tuesday 

 

UEd 

Wednesday 

 

thu 

Thursday 

 

Fri 

Friday 

 

Sat 

Saturday 

 

Sun 

Sunday 

8. 

 

Touch the SET key: the device will exit the procedure. 

9. 

 

Touch the ON/STAND-BY key to exit the procedure beforehand. 

 

6.3 

Restore the factory settings (default) and store customized settings as default 

 

 

N.B. 

-  Check  that  the  factory  settings are appropriate;  see  the  section  CONFIGURATION 

PARAMETERS. 

-  the storing of customized settings overwrites the default. 

 

1. 

 

Touch the SET key for 4 s: the display will show the label “PA”. 

2. 

 

Touch the SET key. 

3. 

 

Touch the UP or DOWN key within 15 s to set the value. 

 

VAL. 

DESCRIPTION 

 

149 

value to restore the factory settings (default) 

 

161 

value to store customized settings as default 

4. 

 

Touch the SET key (or do not operate for 15 s): the display will 

show  the  label  “dEF”  (when  value  “149”  is  set)  or  the  label 

MAP” (when value “161” is set). 

5. 

 

Touch the SET key. 

6. 

 

Touch the UP or DOWN key within 15 s to set “4”. 

7. 

 

Touch the SET key (or do not operate for 15 s): the display will 

show for 4 s “-  -  -“ flashing, then the device will exit the proce-

dure. 

8. 

Interrupt the power supply to the device. 

9. 

 

Touch the SET key 2 s before action 6. to exit the procedure be-

forehand. 