EVCO S.p.A. | EV3221 & EV3231 | Instruction sheet ver. 1.0 | Code 1043221E103 | Page 1 of 2 | PT 44/16
EV3221 & EV3231
Controllers for refrigerated cabinets, undercounters and islands,
with energy-saving strategies
E
ENGLISH
-
Controllers for normal temperature units.
-
Power supply 230 VAC, 115 VAC or 12-24 VAC/DC (according to the model).
-
Incorporated clock (according to the model).
-
Cabinet probe (PTC/NTC).
-
Door switch/multi-purpose input.
-
Compressor relay 16 A res. @ 250 VAC or 30 A res. @ 250 VAC (according to the
model).
-
Alarm buzzer.
-
TTL or RS-485 MODBUS slave port for BMS (according to the model).
-
Cooling or heating operation.
1
MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
-
The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
-
Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
-
In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
N.B.
-
Use cables of an adequate section for the current running through them.
-
To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
PRECAUTIONS FOR ELECTRICAL CONNECTION
-
If using an electrical or pneumatic screwdriver, adjust the tightening torque.
-
If the device has been moved from a cold to a warm place, the humidity may have
caused condensation to form inside. Wait about an hour before switching on the
power.
-
Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS.
-
Disconnect the power supply before doing any type of maintenance.
-
Do not use the device as safety device.
-
For repairs and for further information, contact the EVCO sales network.
3
FIRST-TIME
1.
Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2.
Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3.
Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use.
PAR.
DEF.
PARAMETER
MIN... MAX.
SP
0.0
setpoint
r1... r2
P0
1
probe type
0 = PTC
1 = NTC
P2
0
temperature unit of measurement
0 = °C
1 = °F
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
6.
For the connection in an RS-485 network connect the interface EVIF22TSX or
EVIF23TSX, to activate real time functions connect the module EVIF23TSX (or use
EV3... XRS); see the relevant instruction sheets.
7.
Power up the device.
4
USER INTERFACE AND MAIN FUNCTIONS
4.1
Switching the device on/off
1.
If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED
ON
OFF
FLASHING
compressor on
compressor off
- compressor protection active
- setpoint setting active
defrost active
-
dripping active
HACCP
saved HACCP alarm
-
new HACCP alarm saved
energy saving active
-
-
request for compres-
sor service
-
- settings active
- access to additional functions
active
°C/°F
view temperature
-
overcooling or overheating active
device off
device on
device on/off active
If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
the keypad will lock automatically.
4.2
Unlock keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3
Set the setpoint
Check that the keypad is not locked.
1.
Touch the SET key.
2.
Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default “-50... 50”)
3.
Touch the SET key (or do not operate for 15 s).
4.4
Activate manual defrost (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1.
Touch the UP key for 2 s.
If P4 = 1, defrost is activated provided that the evaporator temperature is lower than the d2
threshold.
4.5
Silence buzzer (if A13 = 1)
Touch a key.
5
ADDITIONAL FUNCTIONS
5.1
Activate/deactivate overcooling, overheating and manual energy saving
Check that the keypad is not locked.
1.
Touch the DOWN key.
FUNCTION
CONDITION
CONSEQUENCE
overcooling
r5 = 0, r8 = 1 and defrost
not active
the setpoint becomes “setpoint -
r6”, for the r7 duration
overheating
r5 and r8 = 1
the setpoint becomes “setpoint +
r6”, for the r7 duration
energy saving
r5 = 0 and r8 = 2
the setpoint becomes “setpoint +
r4”, at maximum for HE2 duration
5.2
View/delete HACCP alarm information
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
LS
view HACCP alarm information
rLS
delete HACCP alarm information
3.
Touch the SET key.
4.
Touch the UP or DOWN key to select an alarm code (when label
“LS” is selected) or to set “149” (when label “rLS” is selected).
COD. DESCRIPTION
AL
low temperature alarm
AH
high temperature alarm
id
door switch alarm
PF
power failure alarm (available in EV3... XRS or if module EVIF23TSX is con-
nected)
5.
Touch the SET key.
6.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
Example of alarm information (e.g. a high temperature alarm).
8.0
critical value (cabinet/ calculated product temperature)
was 8.0 °C/°F
Sta
(available in EV3... XRS or if module EVIF23TSX is connected)
y15
alarm signalled in 2015
n03
alarm signalled in March
d26
alarm signalled on 26 March 2015
h16
alarm signalled at 16:00
n30
alarm signalled at 16:30
dur
h01
alarm lasted 1h
n15
alarm lasted 1h 15 min
5.3
View/delete compressor functioning hours and view compressor start-up
number
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
CH
view compressor functioning hours (hundreds)
rCH
delete compressor functioning hours
nS1
compressor start-up number (thousands)
3.
Touch the SET key.
4.
Touch the UP or DOWN key to set “149” (when label “rCH” is se-
lected).
5.
Touch the SET key.
6.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.4
View the temperature detected by the probes
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
Pb1
cabinet temperature
Pb2
auxiliary temperature (if P4 = 1 or 2)
3.
Touch the SET key.
4.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.5
View the project number and the firmware revision
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB.
DESCRIPTION
PrJ
view the project number
rEU
view the firmware revison
3.
Touch the SET key.
4.
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
6
SETTINGS
6.1
Setting configuration parameters
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “SP”.
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15 s to set the value.
8.
Touch the SET key (or do not operate for 15 s).
9.
Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
6.2
Set the date, time and day of the week (available in EV3... XRS or if module
EVIF23TSX is connected)
N.B.
Do not disconnect the device from the mains within two minutes since the setting of
the time and day of the week.
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select the label “rtc”.
3.
Touch the SET key: the display will show the label “yy” followed
by the last two figures of the year.
4.
Touch the UP or DOWN key within 15 s to set the year.
5.
Repeat actions 3. and 4. to set the next labels.
LAB.
DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
n
month (01… 12)
d
day (01… 31)
h
time (00… 23)
n
minute (00… 59)
6.
Touch the SET key: the display will show the label for the day of
the week.
7.
Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB.
DESCRIPTION
Mon
Monday
tuE
Tuesday
UEd
Wednesday
thu
Thursday
Fri
Friday
Sat
Saturday
Sun
Sunday
8.
Touch the SET key: the device will exit the procedure.
9.
Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3
Restore the factory settings (default) and store customized settings as default
N.B.
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- the storing of customized settings overwrites the default.
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the value.
VAL.
DESCRIPTION
149
value to restore the factory settings (default)
161
value to store customized settings as default
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “dEF” (when value “149” is set) or the label
“MAP” (when value “161” is set).
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or do not operate for 15 s): the display will
show for 4 s “- - -“ flashing, then the device will exit the proce-
dure.
8.
Interrupt the power supply to the device.
9.
Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.