9. REGULATION PARAMETERS
Description of columns in the Table of Parameters
• Par
.:Listofconfigurabledeviceparameters;
• Description: Indicates parameter operation and any possible selections;
• MU: Measurement unit relating to the parameter;
• Range: Describes the interval of values that the parameter can assume. This can be correlated with other instrument
parameters (indicated with the parameter code).
NOTE
:
if the actual value is outside the permitted limits for that parameter (for example, because other parameters
defining the aforementioned limits have been altered), the value of the violated limit is displayed instead of the actual
value;
• Default
:Indicatesthepre-setfactoryconfiguration;
• PW: Indicates the access level for the parameter.
• MODBUS address: Indicates the address of the MODBUS register containing the resource you want to access.
9.1 TABLE OF REGULATION PARAMETERS
Par. Description
MU
Range
Default
SETPOINT Group
SP Temperature setpoint.
°C/°F
r1...r2
0.0
ANALOGUE INPUTS Group
CA1 Probe Pb1 offset.
°C/°F
-25.0...25.0
0.0
CA2 Probe Pb2 offset.
°C/°F
-25.0...25.0
0.0
CA3 Probe Pb3 Offset.
°C/°F
-25.0...25.0
0.0
P0 Type of probe. 0 = PTC; 1 = NTC.
---
0/1
1
P1 Enable decimal point in °C. 0 = No; 1 = Yes.
---
0/1
1
P2
Temperaturemeasurementunit(ifthevalueischanged,thetemperatureparameterlimits
must be reset manually). 0 = °C; 1
=°F.
---
0/1
0
P3
Probe Pb2 function.
0 = Disabled;
1 = D fans;
2
=Fans.
---
0...3
1
P4
Configuration of input Pb3/ID3.
0 = Digital input ID3;
1 = Condenser probe;
2 = Critical temperature probe;
3 = External air probe (display only).
---
0...3
0
P5
Value displayed.
0 = Regulation temperature.
1 = Setpoint.
2 = Probe Pb2 temperature.
3 = Probe Pb3 temperature.
4 = Incoming air temperature.
---
0...4
1
P7
Incoming air coefficient to calculate product temperature (CPT).
CPT = {[(P7 x (incoming air)] + [(100 - P7) x (outgoing air)] : 100}
---
0...10
5
P8 Refresh time display 1.
s
0...250/10
5
TEMPERATURE REGULATION Group
r0 Cooling mode setpoint differential.
°C/°F
0.1...15.0
2.0
r1 Minimum setpoint.
°C/°F
-99.0...r2
-50.0
r2 Maximum setpoint.
°C/°F
r1...199
50.0
r4 Setpoint offset in energy saving added to SET value.
°C/°F
0.0...99.0
0.0
r5 Heating/Cooling regulation. 0 = Cooling; 1 = Heating.
---
0/1
0
r6 Setpoint offset in over-cooling/over-heating.
°C/°F
0.0...99.0
0.0
r7 Duration of over-cooling/over-heating.
min
0...240
0
r8
Downkeyadditionalfunction
.
0 = Disabled;
1 = Over-cooling/over-heating;
2 = Energy saving.
---
0...2
0