![Evco EV3 200 WEB Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/evco/ev3-200-web/ev3-200-web_manual_2441784011.webp)
1143W24E4.00 · EV3 200 Web
03/2021
| 11 |
WARNING
MALFUNCTIONING OF THE EQUIPMENT
•
Performthewiringcarefully,incompliancewithelectromagneticcompatibilityandsafetyrequirements.
•
Makesurethewiringiscorrectfortheapplication.
• Use shielded cables for all I/O signal and communication cables.
• Minimise the length of the connections as much as possible and avoid winding the cables around electrically connected
parts.
•
Thesignalcables(analogueanddigitalinputs,communicationandcorrespondingpowersupplies),powercablesandpower
supply cables for the device must be routed separately.
•
Beforeapplyingthepowersupply,checkallthewiringconnections.
•
Usetherequiredsafetyinterlockswherepersonneland/orequipmenthazardsexist.
•
Installandoperatethisequipmentinacabinetappropriatelyratedforitsintendedenvironmentandsecuredbyakeyedor
tooledlockingmechanism.
• Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for
the rated current and voltage of the particular equipment.
• Do not use this equipment in safety-critical machine functions.
•
Donotdisassemble,repairormodifythisequipment.
• Do not connect wires to unused terminals and/or to terminals labelled “No connection “(N.C.)”.
3.3 DIMENSIONS
33 (1.30)
75 (2.95)
69 (2.71)
59
(2.32)
mm (in.)
Fig. 1.
Dimensions
EV3 200 Web
3.4 INSTALLATION
71 (2
.79)
29 (1.14)
mm (in.)
Fig. 2. Installation EV3 200 WEB