EVCO | 06.08.2021 | AZ
| 11
002_c-pro3OEM_ConnettoriSchedaGiorno_001_0.1_AZ
c-pro 3 OEM
AO4 AO3 AO2 AO1 M9
M8
C1 NO1 C2 NO2 C3 NO3
M7
M6
M5
M4
M3
C4 NO4 C5 NO5
M2
M1 GND 12V
NO6 C6
NC6
ITB GND A+
HV1
HV1
HV2 HV2
B-
C+
C-
PS
PS
5V
2 1
ON
DIHV5 DIHV5
IN
OUT
Pulse - EPB90V
114CP3OEE104
c-pro 3 OEM -
Hardware manual
Electrical connections
WARNINGS FOR ELECTRICAL CONNECTIONS
–
Use cables of an adequate section for the current running through them
–
To reduce any electromagnetic interference connect the power cables as far away as possible from the signal cables
and connect to a CAN, RS-485 MODBUS and INTRABUS networks by using a twisted pair
–
If using an electrical or pneumatic screwdriver, adjust the tightening torque
–
If the device has been moved from a cold to a warm place, the humidity may have caused condensation to form inside.
Wait about an hour before switching on the power
–
Make sure that the supply voltage, electrical frequency and power are within the set limits
–
Disconnect the power supply before doing any type of maintenance
–
Do not use the device as safety device
–
For repairs and for further informations, contact the EVCO sales network; possible returns without label data will not be
accepted
Connectors description
Open frame version
Connector 8
Connector 1
Connector 2
Connector 4
Connector 3
Connector 5
Connector 6
Connector 7
Connector 1
Number
Description
C1
K1 digital output common contact
NO1
K1 digital output normally open contact
(5 A res. at 250 VAC)
C2
K2 digital output common contact
NO2
K2 digital output normally open contact
(5 A res. at 250 VAC)
C3
K3 digital output common contact
NO3
K3 digital output normally open contact
(5 A res. at 250 VAC)
Connector 2
Number
Description
C4
K4 digital output common contact
NO4
K4 digital output normally open contact
(5 A res. at 250 VAC)
C5
K5 digital output common contact
NO5
K5 digital output normally open contact
(8 A res. at 250 VAC)
Connector 3
Number
Description
NO6
K6 digital output normally open contact
(16 A res. at 250 VAC)
C6
K6 digital output common contact
NC6
K6 digital output normally closed contact
Connector 4
Number
Description
HV1
DI1 High voltage digital input
HV1
DI1 High voltage digital input
HV2
DI2 High voltage digital input
HV2
DI2 High voltage digital input
Connector 9
Connector 10