CANBUS CAN port:
-

1,000 m (3,280 ft) with baud rate 20,000 baud

-

500 m (1,640 ft) with baud rate 50,000 baud

-

250 m (820 ft) with baud rate 125,000 baud

-

50 m (164 ft) with baud rate 500,000 baud

according to the factory setting the device automati-
cally detects the baud rate of the other elements mak-
ing the network, on condition that it is one of those
listed before; on afterwards set manually the baud
rate to the same value of that of the other elements

-

USB port: 1 m (3.280 ft).

To wire the device one suggests using the connecting kit
CJAV31 (to order separately): only female removable screw
connection terminal blocks with pitch 3.5 mm (0.137 in)
for conductors up to 1.5 mm² (0.0028 in²) and only fe-
male removable screw connection terminal blocks with pitch
5.0 mm (0.196 in) for conductors up to 2.5 mm²
(0.0038 in²).
To program the device one suggests using the connecting
cables 0810500018 or 0810500020 (to order separately):
the cable 0810500018 is 2.0 m (6.561 ft) long, the cable
0810500020 is 0.5 m (1.640 ft) long.

Operating temperature:

-

from -10 to 55 °C (from 14 to 131 °F) for the built-in
versions

-

from -20 to 55 °C (from -4 to 131 °F) for the blind
versions.

Storage temperature:

 from -25 to 70 °C (from -13 to

158 °F).

Operating humidity:

 from 10 to 90% of relative humid-

ity not condensing.

Control pollution situation:

 2.

Environmental conformity:

-

RoHS 2011/65/CE

-

WEEE 2012/19/EU

-

REACH regulation (CE) n. 1907/2006.

EMC conformity:

-

EN 60730-1

-

IEC 60730-1.

Power supply:

-

24 VAC, 50/60 Hz (±3 Hz), 20 VA max. not isolated

-

20... 40 VDC, 12 W max. not isolated

supplied by a class 2 circuit.
Protect the power supply with a 2 A-T 250 V fuse.
If the device is powered in direct current, it will be neces-
sary to respect the polarity of the power supply voltage.

Rated impulse voltage:

 4 KV.

Overvoltage category:

 III.

Class and structure of software:

 A.

Real time clock:

 incorporated (with lithium primary bat-

tery).
Battery range in absence of power supply: 5 years @ 25 °C
(77 °F).
Drift: 

 30 s/month @ 25 °C (77 °F).

Analog inputs:

 5 inputs:

-

3 which can be set via configuration parameter for
PTC, NTC or Pt 1000 probes

-

3 which can be set via configuration parameter for
PTC, NTC, Pt 1000 probes, 0-20 mA, 4-20 mA, 0-5 V
ratiometric or 0-10 V transducers

Power supply 0-5 V ratiometric transducers: 5 VDC (+0 %,
-12 %), 60 mA max.
Power supply 0-20 mA, 4-20 mA and 0-10 V transducers:
12 VDC (±10 %), 120 mA max.
The maximum current which can be supplied on the whole
from the two power supply is 120 mA.
PTC analog inputs (990 

 @ 25 °C, 77 °F)

Kind of sensor:

KTY 81-121.

Working range:

from -50 to 150 °C (from -58
to 302 °F).

Accuracy:

±0.5 % of the full scale.

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

none.

NTC analog inputs (10 K

 @ 25 °C, 77 °F)

Kind of sensor:

ß3435.

Working range:

from -40 to 120 °C (from -58
to 248 °F).

Accuracy:

-

±0.5 % of the full scale
from -40 to 100 °C

-

±1 °C from -50 to -40 °C
and from 100 to 120 °C.

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

none.

NTC analog inputs (10 K

 @ 25 °C, 77 °F)

Kind of sensor:

NTC type 2.

Working range:

from -40 to 86 °C (from -40 to
186 °F).

Accuracy:

±1 °C.

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

none.

NTC analog inputs (10 K

 @ 25 °C, 77 °F)

Kind of sensor:

NTC type 3.

Working range:

from -40 to 86 °C (from -40 to
186 °F).

Accuracy:

±1 °C

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

none.

Pt 1000 analog inputs (1 K

 @ 0 °C, 32 °F)

Working range:

from -100 to 400 °C (from -148
to 752 °F).

Accuracy:

-

±0.5 % of the full scale
from -100 to 200 °C

-

±2 °C from 200 to -400 °C.

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

none.

0-20 mA and 4-20 mA analog inputs
Input resistance:

 200 

.

Accuracy:

±0.5 % of the full scale.

Resolution:

0.01 mA.

Conversion time:

100 ms.

Protection:

none; the maximum current al-
lowed on each input is 25 mA.

0-5 V ratiometric and 0-10 V analog inputs
Input resistance:

 10 K

.

Accuracy:

±0.5 % of the full scale.

Resolution:

0.01 V.

Conversion time:

100 ms.

Protection:

none.

Digital inputs:

 5 inputs (which can be set with the develop-

ment environment UNI-PRO 3 for NO or NC contact):
-

2 at 24 VAC/DC, 50/60 Hz or 2 KHz optoisolated; the
frequency can be set with the development environment
UNI-PRO 3

-

3 at 24 VAC/DC, 50/60 Hz.

24 VAC/DC, 50/60 Hz digital inputs
Power supply:

-

24 VAC (±15 %), 50/60 Hz
(±3 Hz)

-

24 VDC (+66 %, -16 %).

Input resistance:

 10 K

.

Protection:

none.

24 VAC/DC, 2 KHz digital inputs
Power supply:

-

24 VAC (±15 %), 50/60 Hz
(±3 Hz)

-

24 VDC (+66 %, -16 %).

Input resistance:

 10 K

.

Protection:

none.

Analog outputs:

 3 outputs:

-

2 which can be set via configuration parameter for PWM
or 0-10 V

-

1 which can be set via configuration parameter for
0-20 mA, 4-20 mA or 0-10 V.

PWM analog outputs
Power supply:

10 VDC (+16 %, -25 %), 10 mA
max.

Frequency:

0... 2 KHz.

Duty:

0... 100 %.

Protection:

none.

0-20 mA and 4-20 mA analog outputs
Input resistance:

40... 300 

.

Accuracy:

±3 % of the full scale.

Resolution:

0.05 mA.

Conversion time:

1 s.

Protection:

none.

0-10 V analog outputs
Input resistance:

1 K

.

Accuracy:

±3 % of the full scale.

Resolution:

-

+2 %, -5 % of the full scale

for loads having impedance
from 1 to 5 K

-

±2 % of the full scale for
loads having impedance
> 5 K

.

Digital outputs:

 7 outputs:

-

according to the model:
-

six 3 res. A @ 250 VAC SPST electromechanical
relays (K1... K6)

-

two 24 VAC/DC, 600 mA max. commands for solid
state relay (K1 and K2) and four 3 res. A @ 250 VAC
SPST electromechanical relays (K3... K6)

-

one 3 res. A @ 250 VAC SPDT electromechanical relay
(K7).

The device ensures a double insulation among each connec-
tor of the digital outputs and the remaining parts of the de-
vice.

Type 1 or type 2 actions:

 type 1.

Additional features of type 1 or type 2 action:

 C.

Displays:

 according to the model:

-

none (blind version)

-

4+4 digits custom display (built-in LED version)

-

128 x 64 pixel single colour LCD graphic display (built-in
LCD version).

Communication ports:

 5 ports:

-

1 RS-485 port with MODBUS slave communication pro-
tocol

-

1 RS-485 port with MODBUS master/slave, BACnet MS/
TP communication protocol (which can be set with the
development environment UNI-PRO 3)

-

1 CAN port with CANBUS communication protocol

-

1 USB port

-

1 Ethernet port with MODBUS TCP, Web Server, BACnet
IP communication protocol.

The BACnet communication protocol is in alternative to the
Web Server functionality.
The actual UNI-PRO 3.13 version implements a BACnet®
standardized device profile B-ASC, which doesn’t require the
managing of Scheduler and Calendar objects, instead required
for the B-AAC profile.

Содержание c-pro 3 NODE kilo

Страница 1: ...utenticazione will be published in the EVCO website to support the change in the hardware structure The new UNI PRO version allows backward compatibility with the devices previously manufactured and or delivered while binary projects or applications precompiled with UNI PRO versions older than the 3 23 0 0 will need to be recompiled if used with devices featuring the new hardware structure The dev...

Страница 2: ...icazione la nuova versione UNI PRO 3 23 0 0 La nuova versione UNI PRO garantisce la retro compatibilità con i dispositivi precedentemente prodotti e o consegnati mentre i progetti o applicativi in formato binario realizzati con versioni di UNI PRO precedenti la 3 23 0 0 andranno ricompilati per essere utilizzati con i dispositivi realizzati con la nuova struttura hardware I dispositivi che necessi...

Страница 3: ...Size 142 0 x 128 0 x 60 0 mm 5 590 x 5 039 x 2 362 in W x H x D 8 DIN modules Size refers to the device with the extractable screw termi nal blocks properly plugged Method of mounting control on DIN rail 35 0 x 7 5 mm 1 377 x 0 295 in or 35 0 x 15 0 mm 1 377 x 0 590 in Degree of protection IP20 on the whole IP40 the front Connections only male removable screw connection terminal blocks with pitch ...

Страница 4: ...orking range from 40 to 120 C from 58 to 248 F Accuracy 0 5 of the full scale from 40 to 100 C 1 C from 50 to 40 C and from 100 to 120 C Resolution 0 1 C Conversion time 100 ms Protection none NTC analog inputs 10 KΩ 25 C 77 F Kind of sensor NTC type 2 Working range from 40 to 86 C from 40 to 186 F Accuracy 1 C Resolution 0 1 C Conversion time 100 ms Protection none NTC analog inputs 10 KΩ 25 C 77...

Отзывы: