EVCO S.p.A.
c-pro 3
| Hardware manual ver. 2.0 | Code 114CP3E204
page 46 of 86
Parameters (1)
AI3
- - -
- - -
- - -
NTC
kind of probe analog input 3
PTC =
PTC
probe
NTC =
NTC
probe
0-20mA = 0-20
mA
transducer
4-20mA = 4-20
mA
transducer
0-5V
= 0-5 V ratiometric transducer
0-10V
= 0-10 V ratiometric transducer
PT1000 = Pt
1000
probe
Parameters (1)
AI Err Time
0
240
s
2
analog inputs time-out (after this time without
communication with an analog input, the
controller signals the analog input error)
Parameters (1)
AO1
- - -
- - -
- - -
PWM
kind of signal analog input 1
PWM =
PWM
(Pulse
With
Modulation)
Parameters (1)
AO2
- - -
- - -
- - -
0-10V
kind of signal analog input 2
0-20mA = 0-20
mA
4-20mA = 4-20
mA
0-10V =
0-10
V
Parameters (1)
AO3
- - -
- - -
- - -
0-10V
kind of signal analog input 3
0-20mA = 0-20
mA
4-20mA = 4-20
mA
0-10V =
0-10
V
Parameters (1)
CosPhi 10us
- - -
- - -
- - -
- - -
reserved
Parameters (2)
[ press button
RIGHT to
show it ]
I/O
Timeout 1 240 s 60
time-out of the CANbus communication for
the test of the remote values of the I / O
(after this time without CANbus
communication, the I / O of the controller is
disabled)
Parameters (2)
[ press button
RIGHT to
show it ]
En. Prg Level
- - -
- - -
- - -
NO
enabling the access to the first level page
pressing a combination of buttons
YES
= yes, operating as follows:
-
keep pressed 3 s button
ENTER to gain access
to the first page of
level
1
- keep pressed 3 s
buttons
ENTER
and
ESC to gain access to
the first page of level 2
- keep pressed 3 s
buttons LEFT and
RIGHT to gain access to
the first page of level 3