39
Controller User Manual
In order to view or perform an I/O test, the eco-Air unit must be switched off (Figure 28). The test must first be enabled. After being
enabled, the digital outputs may be manually enabled or disabled. Note that enabling an output will cause the device attached to
the output to function.
When equipped with EC fan motors, it may be necessary to replace a fan motor. When an EC fan motor ships from the
manufacturer, it is programmed with a default Modbus address of 1. Once the replace fan configuration submenu is chosen,
navigate to the fan that needs to be replaced. Use the
UP
or
DOWN
buttons to navigate between the different fan addresses. Next,
set the current address to 1 and set change now to YES. After a several minutes, several messages will be displayed as described
in Table 27. Cycle power to both the EVAPCO Controller and the newly replaced EC fan motor. The new EC fan will now be
programmed to the proper Modbus address.
Figure 70
The I/O Test Screen.
Figure 71
An example of replacing EC fan motor number four.
Rebooting fan firmware
Fan electronics are rebooting
Controller is attempting to reconnect with fan motor
Fan motor is programmed with new address
Message
Action
Table 27
The messages seen while assigning a new address to an EC fan motor.
Reboot FW
Wait offline
Wait online
End procedure