6. Trouble Shooting
FAULT
CAUSE
RECOMMENDED FIX
Not running
No LED display
No power to unit
• Try on both 12V DC and 240 AC
• Maybe a faulty lead
• Try a different power supply
• Check circuit breaker or fuse
Faulty electronic
component
Contact Evakool
(07) 5492 7777
LED display on
but not running
Faulty electronic
component
Contact Evakool
(07) 5492 7777
LED display on,
compressor running,
not cooling
Compressor or
refrigerant problem
Contact Evakool
(07) 5492 7777
LED display on
Fault light flashing
Refer to chart below
The unit has its own built in fault
finding system depending on
how many fashes per 5 flashes
Led display shows
Error codes
ER1
ER2
This is a thermistor issue
contact Evakool (07) 54927777
Refers to fault light error
1 Flash: LOW VOLTAGE ERROR
Cause:
• Battery is flat . Check with multimeter, 12 .70 Volts 100% charge, 12 .05V 50% charge,
10 .50V 0% charge .
• Faulty supply lead . Check that the plug and lead are not broken or frayed .
• Supply wiring not the correct size (refer to cable sizing chart below) .
• To rule out that the fridge is not faulty, try running it on a different power source, either
on 240 Volt supply or a different vehicle or battery .
2 Flash: FAN ERROR
Cause:
• Condenser fan drawing too many amps (over 1-amp peak) . Requires a replacement fan,
contact Evakool .
Содержание MAXI TRAC MT-45