background image

HA 026773

Page 1 of 4

Issue 1.3 June 2000

Installation Manual and

User guide

PC300 Process control system

The PC300 process control system uses highly reliable and field tested PC3000 components.  The unit
includes an integral power supply, the Local Controller Module ’plus’ and two free module positions for
installing other I/O modules.  The PC300 has a steel case construction and is designed for backplane
mounting.

Specification

General

Supply voltage range

85 to 132V ac rms
176 to 240V ac rms
Selected by external wiring option

Supply frequency range

48 - 62 Hz

VA requirements

< 40VA for fully loaded rack

Power Supply Output

50W total, 24V @ 1.6A, 5V @ 2.5A

Inrush Current

25A, single cycle, cold start, high
line

Power supply hold up
time

>20ms at minimum line voltage and
maximum load (>100ms typical)

Input protection

RFI Input filter, transient protection

Replaceable Fuse Rating

1.6A time lag

Mechanical

Height

193 mm, inc. mounting brackets

Depth

203 mm, inc. mounting brackets

Width

316 mm

Mounting

Bulkhead mounting

Casing

Robust Metal case to IP20

Module capacity

2 single with I/O slots

Ventilation Space

25mm free space above and below

Environmental

Operating Temperature

0 to 50

C

Storage Temperature

-20 to 70

C

Relative Humidity

5 to 95 % non-condensing

Weight

5.25 Kg

Weight support brackets

0.4 Kg each

EMC

Emissions

EN50081-2: 1994

Immunity

EN50082-2: 1992

Safety

EN61010-1: 1993/A2: 1995
Installation cat II, Pollution degree 2

LCM-Plus

RAM

256K base RAM

Slot 1

512K standard

Slot 2

128k for special FB (optional)

Communications Ports

Ports A & B

User ports

Port C

PC3000 extension rack port

Standard

Ports A & B

RS422

Port C

RS485 / RS422 (jumper selectable)

Baud Rates

Ports A & B

300 to 38.4k

Port C

300 to 115k

Protocols

Software selectable
(2 of ports A,B,C)

Available I/O modules

Analogue Input

0-100mV
0-10V
0-20mA
Thermocouple (J,K,R,S,B,Pyro)
PT100 Resistance Thermometer
Frequency 0-10kHz
Zirconia probe

Analogue Output

0-5V, 0-10V, -10 to +10V etc
4-20mA, 0-20mA etc

Digital Inputs

5Vdc
25Vdc
24Vac
85-264Vac
Volt Free

Digital Out

Logic
Relay (N/O)

Pulse Input

200kHz - 5v, 12v(selectable)

Содержание PC300

Страница 1: ...th 203 mm inc mounting brackets Width 316 mm Mounting Bulkhead mounting Casing Robust Metal case to IP20 Module capacity 2 single with I O slots Ventilation Space 25mm free space above and below Environmental Operating Temperature 0 to 50o C Storage Temperature 20 to 70o C Relative Humidity 5 to 95 non condensing Weight 5 25 Kg Weight support brackets 0 4 Kg each EMC Emissions EN50081 2 1994 Immun...

Страница 2: ...nt to configure jumpers or switches to set I O module addresses The module address is read directly from the backplane Compatability The PC300 is directly compatible with and a subset of the PC3000 The two products share I 0 cards programming tools and instruction manuals Manuals PC3000 instruction manuals are used for the PC300 219 316 44 53 30 42 120 193 166 44 16 182 Alternate Bracket Position ...

Страница 3: ...sor status run and fault system diagnostic functions and communication channel activity are provided System and IOC status LED s F Fault R Run Diagnostic LED s Consult PC3000 Hardware Reference Manual for details Communication LED s A B C Serial channel communication activity D Extension rack communication activity 3RZHU 6XSSO 8QLW 368 nc nc nc nc C Common N O Normally Open Health N C Normally Clo...

Страница 4: ...ecome disconnected should excess tension be applied to the mains cable 3 It is recommended that crimps be used to terminate the wires before they are inserted into the terminal blocks 4 The Mains supply fuse within the Power supply unit is replaceable and should only be replaced with a fuse of the same type and rating In no conditions should the fuse be replaced with one of a higher rating 5 Whene...

Отзывы: