Chapter 5 Terminal Descriptions
5 - 6
582/583/5831
SW7
SW8
(OFF)
(OFF)
(OFF)
(ON)
(ON)
(OFF)
(ON)
(ON)
- Stopping Mode
:
:
:
:
Coast to Stop.
Ramp down to Stop.
Ramp to zero followed by 2 sec DC holding pulse.
DC Injection Braking. (See Note 2).
SW9
Ramp Hold
:
This switch should normally be off. (See Note 3).
SW10
SW11
SW12
Power
Output
Drive
(OFF)
(ON)
:
0.37kW
0.55kW
582
0.37/0.55kW
1
(OFF)
(ON)
:
0.55kW
0.75kW
582
0.55/0.75kW
1
(OFF)
(OFF)
(ON)
(ON)
(OFF)
(ON)
(ON)
(ON)
(ON)
:
:
:
0.75kW
1.1kW
1.5kW
583
1.1/1.5kW
1
(OFF)
(ON)
(OFF)
(ON)
(ON)
(OFF)
:
:
1.5kW
2.2kW
583
1.5/2.2kW
1
(OFF)
(OFF)
(ON)
(ON)
(OFF)
(ON)
(ON)
(ON)
(ON)
:
:
:
0.37kW
0.55kW
0.75kW
5831
0.75kW
1
(OFF)
(OFF)
(ON)
(ON)
(OFF)
(ON)
(ON)
(ON)
(ON)
:
:
:
0.75kW
1.1kW
1.5kW
5831
1.5kW
1
NOTES:
1.
Controllers are shipped with switches set to the lower rating. Set switches to the required
rating before use. Setting of the switches on the 583 1.1/1.5kW version to 2.2kW will
cause damage and invalidate the warranty.
2.
DC injection braking may be selected by setting switches 7 and 8 to the ‘on’ position.
When a stop command is received, the drive will apply a low frequency braking current to
the motor, until the shaft is almost at a standstill. The amount of braking is controlled by
the current limit setting.
DC current is then applied for a short time, to bring the shaft finally to a standstill. This is
controlled by the boost adjustment.
3.
To achieve very fast ramp up rates, e.g., 0.1 seconds, it may be necessary to set this switch
to ‘on’.
Содержание 582
Страница 7: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 20: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 38: ...Figure B Mounting Details for Filter Part Number CO389108 ...
Страница 39: ...Figure C Mounting Details for Filter Part Number CO389110 ...