48 Part number HA028582. Issue 6.0 May-07
5.8
Programmer
‘
TI.CFG’ = ‘ProG
’. Function code CP contains a
four segment programmer where each segment
consists of a controlled ramp rate to a target setpoint
followed by a dwell at that setpoint. These values are
set by the user. The program profile is shown in the
diagram
below.
Notes:-
1.
When a step change is required, set ramp rate to
‘OFF’.
2.
Where ramp/dwell pairs are not required, set the
ramp rate to ‘OFF’ and the TSP the same as the
preceding segment
3.
TIMER END - when the end type is SP2, Timer
END does not occur until the ramp is complete
or SP2 is achieved. It is more usual to use a
DWELL (default) or RESET end type
4.
A single program event output is also available.
To use this refer to the engineering manual.
OFF
Program RUNNING
Starts at
Current
WSP
RESET
RUN
END
Temperature
SP2
Time
SP1
Ramp to
TSP1 at
RMP1
End Type
Dwell
Ramp to
TSP2 at
RMP2
DWEL 1 DWEL.2 DWEL 3 DWEL4
Ramp to TSP3
at RMP3
Ramp to TSP4
at RMP4
SP2 (servo from PV)
Off
Reset
Содержание 3200
Страница 1: ...3200PID Temperature controllers User Guide Manuel Utilisateur Bedienungsanleitung ENG FRA GER ...
Страница 57: ...3200Régulateurs de température PID Manuel Utilisateur FRA ...
Страница 58: ......
Страница 116: ...58 3200 Guide utilisateur HA028582FRA Indice 6 0 mai 07 ...
Страница 117: ...3200PID Temperaturregler Bedienungsanleitung GER ...
Страница 118: ......
Страница 173: ......