Flue and Chimney connection to your stove

The outlet from the chimney should be above the roof of the building in accordance with the provisions of Building Regulations
Approved Document J.

If installation is into an existing chimney then it must be sound and have no cracks or other faults which might allow fumes
into the house. Older properties, especially, may have chimney faults or the cross section may be too large i.e., more than
230 mm x 230 mm. Remedial action should be taken, if required, seeking expert advice. If it is found necessary to line the
chimney then a flue liner suitable for solid fuel must be used in accordance with Building Regulations Approved Document
J.

Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of the stove.

If the stove is fitted in place of an open fire then the chimney should be swept one month after installation to clear any
soot falls which may have occurred due to the difference in combustion between the stove and the open fire.

If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations Approved
Document J or a twin walled insulated stainless steel flue to BS 4543 can be used. These chimneys must be fitted in accordance
with the manufacturer’s instructions and Building Regulations.

A single wall metal flue pipe is suitable for connecting the stove to the chimney but is not suitable for using for the

complete chimney. The chimney and connecting flue pipe must have a minimum diameter of 150 mm and its dimension
should be not less than the size of the outlet socket of the stove. Any bend in the chimney or connecting flue pipe should
not exceed 45

°

.  90

°

 bends should not be used other than  within 150 mm of stove rear flue outlet.

SOOT DOOR WHEN
FIXED AGAINST

OUTSIDE WALL

Содержание CHEW

Страница 1: ...1 OPERATION AND INSTALLATION MANUAL CHEW SHEPPY Multi fuel and SE models...

Страница 2: ...modification to suit particular local site conditions STOVE PERFORMANCE TESTING Eurostove Chew Sheppy stoves are approved and tested in accordance with EN 13240 Output wood fuel Efficiency CO 13 o2 R...

Страница 3: ...IMPORTANT WARNING This stove must not be installed into a chimney that serves any other heating appliance There must not be an extractor fan fitted in the same room as the stove because this can cause...

Страница 4: ...fitted in place of an open fire then the chimney should be swept one month after installation to clear any soot falls which may have occurred due to the difference in combustion between the stove and...

Страница 5: ...sh off with damp cloth If the stove has not been used for some time the flue should be checked for blockages before use Do not modify the appliance only use spares authorised by the manufacturer B C E...

Страница 6: ...les regarding the minimum distance to non flammable walls Eurostove recommend leaving a gap of at least 10 cm behind and to sides of stove Eurostove Insulated chambers Eurostove Stoves are lined with...

Страница 7: ...venting the door seal cord around the door from sticking and coming away from the door Once the heat resistant paint has hardened the smell will disappear This stove is NOT designed to be used with th...

Страница 8: ...for smoke control areas see page 4 alterations should not be attempted Eurostove smoke control stoves should not be burnt with the door left open The refuelling procedure allow the newly charged fuel...

Страница 9: ...wood Newly cut wood should be stacked and air dried under cover for two years before being used as firewood Do not burn liquid fuels drift wood finished sawn wood pallet wood chipboard plywood varnish...

Страница 10: ...otect your hand from possible heat The handle has push pull motion as shown above When shutting the door push the door closed and push handle firmly until the door latches PARTS Always use the operati...

Страница 11: ...ind it and this must be cleaned out Check the quality of all insulated panels and replace any which are damaged or cracked replace stove door rope cord in the door Check glass is correctly positioned...

Страница 12: ...moke or odour a Weak chimney draft b check for blockages in the flue pipe chimney c check the height of the chimney relative to the surroundings 6 Soot in the chimney a The firewood may be too wet b i...