6. POSSIBLE ERRORS IN THE CONTROLLER OPERATION
6.1. A selected zone is not heating
–
closed valve or inactive pump
Check:
◼
Whether the heating season is switched on,
◼
Whether the correct date (day of the week) and time is set,
◼
Whether heating is active in the schedule for the current day of the week and time,
◼
In the system with a weather compensator
–
whether the outdoor temperature reading
is correct and whether the temperatures are set correctly,
◼
Whether DHW priority heating is switched off,
◼
In the system without room thermostat
–
whether it is switched off in the controller,
◼
In the system with a room thermostat
–
whether it is switched on and correctly
connected to the controller,
◼
Whether the mixer is not connected inversely and whether it is not jammed,
6.2. A selected zone is subject to overheating
Check:
◼
Whether the valve is not blocked,
◼
Whether the mixer actuator is operating,
◼
Whether the actuator cables are connected properly,
◼
The value of mixer dynamics.
7. DIMENSIONS
8. TECHNICAL DATA
Supply: 230 V 50 Hz
Maximum power consumption: 4 W
Maximum output load: 100 W (each output)
Temperature adjustment range:
◼
CH zones from 5°C to 90°C
◼
DHW circuit from 5°C to 90°C
Temperature measurement range: -
30°C...120°C
Temperatu
re control and reading accuracy: 1°C
Operation tem
perature range: 0...40°C
Storage temperature range: 0...55°C
Ingress protection rating: IP20, Protection Class II
Color: gray, RAL7035
Mounting method: 35mm DIN rail-mounted, inside electrical cabinets
Alarm output: 230 V 50 Hz
Boiler output: voltage-free type, NO/NC, maximum load: 4A 230V 50Hz
Pump power outputs: 230 V 50 Hz
Power outputs of mixer actuators: 230 V 50 Hz
Controller weight: 545 g