EUROSTER 1100Z – USER MANUAL

2

a. mounting of the controller:

the   controller   is  fixed  directly  to   the   wall   or  to   any  other   support   with  two   screws 
(plastic plugs c/w screws are part of delivery) 

the cables extending from the controller are fixed to the wall with cable clips

b. mounting of the temperature sensor:

the   sensor   is   NOT   intended   for   immersion   in   liquids   and   installation   on 
breechings (flues between the boiler and chimney)

install the heating water temperature sensor on the bare outlet pipe of the boiler (as 
close to the boiler as possible) or on the hot water cylinder

install the DHW temperature sensor on the hot water cylinder (cable marked with a 
black sleeve)

c. connecting of the power supply cable to the heating water circulating pump:

connect the yellow or yellow/green wire (protective conductor) to terminal (

)

connect the blue wire to terminal (N) 

connect the brown wire to terminal (L) 

d. connecting of the power supply cable to the DHW circulating pump (marked with a 

black sleeve):

connect the yellow or yellow/green wire (protective conductor) to terminal (

)

connect the blue wire to terminal (N) 

connect the brown wire to terminal (L) 

e. check-up of connections:

make sure the connections have been made as indicated and secure the cover of the 
pump motor terminal box

f. connection of the controller:

upon securing the cables against accidental pullout, 

connect the power supply cable 

to a 230V/50Hz grounding socket.

IMPORTANT:

  At   the   mounting   location   of   the   controller   ambient   temperature   should   not 

exceed 40ºC.

3. OPERATION

After switching on the controller allow ca. 60 sec. for the controller to become fully 
operational

a. start up:

set the left-hand toggle switch (~) to position I,

upon energising all the segments of the display light up for ca. 2 seconds,

the current temperature, as measured by the sensor is displayed and the controller 
operates according to the factory settings (temperature limit of 50°C).

b. description of display functions

display continuously on – current temperature, as measured by the sensor,

blinking display – temperature setpoint,

red LED on – controller is switched to DHW mode

green LED on – controller is switched to heating mode

dot appears after the second figure – DHW priority is on

c. viewing of DHW temperature

for viewing the DHW temperature simultaneously press and release the two switches. 
The current temperature, as measured by the DHW sensor will be displayed. After 5 

sec. the heating water temperature will return to the display.