LAS Level Alarm System

2/4

Installation & Electrical Connections

The alarm unit is designed for
four-screw wall mounting on a
160mm x 110mm pitch.

 It is recommended that the unit
is not mounted in a location where
it is exposed to direct sunlight.

All wiring must be in suitable cable
for the site conditions.

The installation must comply with
the relevant regulations of the
electrical supply authority
concerned together with any other
statutory requirements which may
affect the complete installation.

3/4

Float Switch Installation

Pass the float switch lead through the tank/cable
gland assembly to give the desired alarm switchpoint
and tighten the cable gland.

Fit  the  float switch assembly through the 1" BSP
tank gland in the tank.

Should the float switch lead require extension,  fit a
PVKA extension cable connector to the float switch
lead and run the length of additional cable from the
PKVA connector to the TA3 unit.

Dimensions

PKVA

Extension

Cable

Connector

Extension
Cable
(2 Core)
supplied
by
Installer

Weight

Cable Gland

Adjust Cable

Gland to set

Alarm Point

LAS 3

Alarm Unit

Float

Circlip

Turn Float

upside down

for Low

Level Alarm

(remove

Circlip

to alter)

Float Switch Assembly

EUROGAUGE

...the level people

User Guide

LAS Level Alarm System

175

76

125

Fixing centres:- 160 x 110mm

24Vdc 

or

 85-265Vac Version

Battery Version

Tank Full

Float Switch

Tank Empty

Float Switch

Bund Full

 Float Switch

IP1

IP2

IP3

IP1

IP2

IP3

Tank Full

Float Switch

Tank Empty

Float Switch

Bund Full

Float  Switch

Live

Neutral

Earth

+24Vdc

0V

Closed when Tank Full

Common

Open when Tank Full

Closed when Bund Full

Common

‘All Alarm contacts are voltage free’

Closed when Tank Empty

Common

Open when Tank

Empty

Tank Full

Alarm

Contacts

Bund Full

Alarm

Contacts

Open when Bund Full

Tank Empty

Alarm

Contacts