Instruction Manual ZHK
V07-21.0
37/140
Figure 34:
Solid foundation and strip foundation
AHUs must weigh down the foundation on the base frame in longitudinal and cross direction either
in strips or points. It is important to distinguish whether the AHU is resting on the base frame, or
whether it is equipped with device feet supplied by EUROCLIMA.
The maximum permissible load limits per unit foot must not be exceeded and are as follows:
per unit foot with height adjustment
without
rubber base (see
max. 500 kg
per unit foot with height adjustment
with
max. 300 kg
Table 6:
Max. permissible load limit for unit feet
Figure 35:
Height adjustable unit foot without rubber
base
Figure 36:
Height adjustable unit foot with rubber base
Содержание ZHK