29
Indoor Unit AWR512HL
Outdoor Unit AER512SH
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 – 240V ~ 50Hz
Rating Conditions Running Amps. A 0.13 /
0.14 0.30
/
0.32 5.8 / 5.8 6.2 / 6.3
Power Input kW 0.029 / 0.033 0.066 / 0.076 1.22 /
1.26 1.31 /
1.37
Full Load Conditions Running Amps. A 0.13 /
0.14 0.30
/
0.32 7.3 / 7.0 7.8 / 7.5
Power Input kW 0.029 / 0.033 0.066 / 0.076 1.56 /
1.57 1.65 /
1.68
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 – 240V ~ 50Hz
Rating Conditions Running Amps. A 0.13 /
0.14 0.30
/
0.32 5.9 / 5.9 6.3 / 6.4
Power Input kW 0.029 / 0.033 0.066 / 0.076 1.24 /
1.29 1.33 /
1.40
Full Load Conditions Running Amps. A 0.13 /
0.14 0.30
/
0.32 7.6 / 7.3 8.0 / 7.7
Power Input kW 0.029 / 0.033 0.066 / 0.076 1.61 /
1.62 1.70 /
1.73
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.