Operating Instructions Safety Systems
MGB2-I-BP.-… / MGB2-I-BR.-…
26
(translation of the original operating instructions) 2530674-02-03/21
12.4. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of devices and the current required for
the outputs. The following rules apply:
Max. current consumption of an individual device I
max
I
max
= I
UB
+ I
FO1A+FO1B
I
UB
= Device operating current (80 mA) + monitoring outputs (4 x max. 50 mA) + control elements
I
FO1A+FO1B
= Load current of safety outputs FO1A + FO1B (2 x max. 150 mA)
BR
Max. current consumption of a switch chain
Σ
I
max
with star wiring
Σ
I
max
= I
FO1A+FO1B
+ n x I
UB
+ n x monitoring outputs
n
= Number of connected devices
Assignment of the currents to the fuse circuits
Current
Fuse circuit F1
Fuse circuit F2
I
UB
80 mA
I
OD,OT,OL,OI
= (4 x max. 50 mA)
I
control elements
= max. 10 mA
(per control element)
I
indicators
= max. 5 mA
(per indicator)
I
FO1A+FO1B
(2 x max. 150 mA)
12.5. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì
On the use of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connecting cables:
Parameter
Value
Unit
Conductor cross-section, min.
0.25
mm²
R max.
60
W
/km
C max.
120
nF/km
L max.
0.65
mH/km