Operating Instructions
Safety Systems with Locking ESL-IH-AR
16
(translation of the original operating instructions) 119138-05-10/15
8.8. Connection of a single AR device
If a single AR device is used, connect the device as shown in
Figure 3
. Monitoring outputs can be routed to a control system.
The switch can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 seconds.
The RST input must be connected to 0 V if it is not used.
WARNING
In case of an error, loss of the safety function through incorrect connection.
Ì
To ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated.
Important!
The example shows only an excerpt that is relevant for connection of the ESL system. The example
illustrated here does not show complete system planning. The user is responsible for safe integration
in the overall system. Detailed application examples can be found at www.euchner.de. Simply enter
the order number in the search box. All available connection examples for the device can be found
under “Downloads.”
GND
DC 24 V
ESL-I-AR #1
FI1B
1
UB
2
FO1A
3
FO1B
4
M12 plug-connector
(8-pin)
OD
5
FI1A
6
0V
7
RST
8
-K1
-K2
-M1
M
A1
A2
A1
A2
13
14
13
14
Figure 3:
Connection example for separate operation of an ESL-I-AR