12. Status and fault displays
The card holder’s LED illumination indicates the individual status and error messages. Detailed error messages can be
output on the touch panel.
Key to symbols
LED not illuminated
LED illuminated
5 Hz
LED flashes at 5 Hz
3 x
LED repeatedly flashes three times
LEDs flash alternately
12.1. Smartcard status and fault displays
Status
code
ENUM in .NET
‘KeyStatus’
Status/error
Meaning
LED indicator
Troubleshooting
yellow
green
0x00
NoKey
Card not inserted or cannot
be read.
The device is ready for operation. No
card is inserted or card cannot be read.
Not an error
0x01
ValidKeyInsert
Card inserted. Card valid.
The inserted card was checked. The
card is valid.
Not an error
0x02
KeyInvalid
Invalid authentication
The card is valid, but an authentication
parameter does not match the pre-
scribed values.
Use card with valid parameters
0x03
KeyLocked
Card blocked
The card can be read but is locked.
Use a valid card.
0x04
KeyExpired
Expired validity date of the
card
The card can be read, but the validity
date has expired.
Use a valid card or extend the
validity date.
0x05
KeyUnknownData-
Structure
Invalid data structure
The card can be read, but its data
structure is invalid.
Card does not belong to this ma-
chine. Use a valid card.
0x06
InvalidFileContent
File error
The file content is invalid and cannot be
read. The file is not safe (security).
Card is faulty or does not belong to
this machine. Use a valid card.
0x07
FileError
File error
At least one data record on the card is
invalid and cannot be read. The file is
not safe (security).
Card is faulty or does not belong to
this machine. Use a valid card.
0x08
KeyTypeNotSup-
ported
Invalid card type
The card can be read, but the card type
is invalid.
Card does not belong to this ma-
chine. Use a valid card.
0x09
KeyCommuncation
Error
Communication error
Disrupted communication with the touch
panel. There may be an EMC fault.
6 x
1. Switch the device off.
2. Check the connecting cables to
the touch panel and to the safe
control system.
3. Restart the device.
Contact the manufacturer if the
problem persists.
100
NoKeyWithFallback
Timeout
No card inserted, and fallback
timeout is activated.
Only in .Net library: no card inserted.
The device will switch to a different safe
operating mode when the fallback timer
elapses.
Insert a valid card with the appropri-
ate authorization within the timeout
period.
101
KeyUIDUnreadable
UID of the inserted card can-
not be read.
Only in .Net library: the unique identifier
(UID) of the card cannot be read.
Use a valid card.
102
KeyInMaximumMO
NotDeterminable
Error when reading the highest
permissible operating mode.
Only in .Net library: the highest permis-
sible operating mode of the inserted
card cannot be read.
Use a valid card.