12.  Status and fault displays

The card holder’s LED illumination indicates the individual status and error messages. Detailed error messages can be 

output on the touch panel.

Key to symbols

LED not illuminated

LED illuminated

 

5 Hz

LED flashes at 5 Hz

 

3 x

LED repeatedly flashes three times

 

 

LEDs flash alternately

12.1.  Smartcard status and fault displays

Status 

code

ENUM in .NET 

‘KeyStatus’

Status/error

Meaning

LED indicator

Troubleshooting

yellow

green

0x00

NoKey

Card not inserted or cannot 

be read.

The device is ready for operation. No 

card is inserted or card cannot be read.

Not an error

0x01

ValidKeyInsert

Card inserted. Card valid.

The inserted card was checked. The 

card is valid. 

Not an error

0x02

KeyInvalid

Invalid authentication

The card is valid, but an authentication 

parameter does not match the pre-

scribed values.

Use card with valid parameters 

0x03

KeyLocked

Card blocked

The card can be read but is locked.

Use a valid card.

0x04

KeyExpired

Expired validity date of the 

card

The card can be read, but the validity 

date has expired.

Use a valid card or extend the 

validity date.

0x05

KeyUnknownData-

Structure

Invalid data structure

The card can be read, but its data 

structure is invalid.

Card does not belong to this ma-

chine. Use a valid card. 

0x06

InvalidFileContent

File error

The file content is invalid and cannot be 

read. The file is not safe (security).

Card is faulty or does not belong to 

this machine. Use a valid card.

0x07

FileError

File error

At least one data record on the card is 

invalid and cannot be read. The file is 

not safe (security).

Card is faulty or does not belong to 

this machine. Use a valid card.

0x08

KeyTypeNotSup-

ported

Invalid card type

The card can be read, but the card type 

is invalid.

Card does not belong to this ma-

chine. Use a valid card. 

0x09

KeyCommuncation 

Error

Communication error

Disrupted communication with the touch 

panel. There may be an EMC fault.

 

6 x

1. Switch the device off. 

2. Check the connecting cables to 

the touch panel and to the safe 

control system. 

3. Restart the device.

Contact the manufacturer if the 

problem persists.

100

NoKeyWithFallback 

Timeout

No card inserted, and fallback 

timeout is activated.

Only in .Net library: no card inserted. 

The device will switch to a different safe 

operating mode when the fallback timer 

elapses. 

Insert a valid card with the appropri-

ate authorization within the timeout 

period.

101

KeyUIDUnreadable

UID of the inserted card can-

not be read.

Only in .Net library: the unique identifier 

(UID) of the card cannot be read.

Use a valid card.

102

KeyInMaximumMO 

NotDeterminable

Error when reading the highest 

permissible operating mode.

Only in .Net library: the highest permis-

sible operating mode of the inserted 

card cannot be read. 

Use a valid card. 

Содержание EKS2

Страница 1: ...EN Operating Instructions Electronic Key System for selection of operating mode EKS2 ...

Страница 2: ...and warranty 7 5 General safety precautions 7 6 Function 7 7 Smartcards 8 8 Mounting 8 9 Electrical connection 9 9 1 General notes 9 9 2 Notes about 9 9 3 Terminal assignment 10 10 Setup 10 11 Operation 10 12 Status and fault displays 11 12 1 Smartcard status and fault displays 11 12 2 EKS2 status and fault displays 12 12 3 Firmware status display 13 13 Technical data 14 13 1 Technical data for EK...

Страница 3: ...ions Ì knowledge about the applicable regulations on operational safety and accident prevention 1 3 Key to symbols Symbol depiction Meaning DANGER WARNING CAUTION Safety precautions Danger of death or severe injuries Warning about possible injuries Caution slight injuries possible NOTICE Important Notice about possible device damage Important information Tip Useful information 1 4 Supplementary do...

Страница 4: ...connection components On the use of unsuit able smartcards or other connection components EUCHNER provides no warranty for safe function Important Ì The user is responsible for the proper integration of the device into a safe overall system For this purpose the overall system must be validated e g in accordance with EN ISO 13849 2 Ì Use only components that are permissible in accordance with the t...

Страница 5: ...operating mode can lead to the safety functions of the selected operating mode not being activated in the machine A system for selection of operating mode can be subdivided into the following subfunctions according to EN ISO 16090 1 for example Ì Access system Ì Selection system Ì Activation system Incorrect behavior or an error in the selection system subfunction can lead to the safety function o...

Страница 6: ...H 0FF0H 3333H 33CCH 3C3CH Setting outputs to safe control system Selecting operating mode Checking selection Confirming selected operating mode Fig 2 Data structure of selection of operating mode To fulfill the safety function of the overall selection of operating mode system a suitable activation system must be connected to the safe outputs of the device A suitable activation system is a safe con...

Страница 7: ...ce schedule 6 Function The device is part of a higher level overall system for selection of operating mode on safe control systems The device consists of a reader and various smartcards Authorizations for selecting various operating modes are stored on the smartcards After being read in the reader the smartcard is checked for validity based on specific parameters If the smartcard is rec ognized as...

Страница 8: ...ce MO Service Automatic mode Setup Automatic mode with manual intervention Automatic mode with manual intervention without enabling device Service mode 3796652 Mode Master MO1 Automatic mode 8 Mounting Assembly instructions are included with the device and form part of these operating instructions Observe the following points during mounting Ì Install the reader on the side of the touch panel If t...

Страница 9: ...uits Ì Ensure that to avoid EMC interference the physical environmental and operating conditions at the installation site of the device comply with the requirements according to the standard EN 60204 1 2016 section 4 4 2 EMC Ì Pay attention to any interference fields from devices such as frequency converters or induction heating systems Observe the EMC notes in the manuals from the respective manu...

Страница 10: ...there is an error in the device or in the cable installa tion The safe control system must be capable of reacting to such errors in accordance with the machine s risk assessment Ì When the device is reset the setting of an output can be delayed by up to 5 s Operating mode MO1 is selected automatically after the reset 11 Operation Important If the smartcard is removed from the reader in operating m...

Страница 11: ...ard does not belong to this ma chine Use a valid card 0x06 InvalidFileContent File error The file content is invalid and cannot be read The file is not safe security Card is faulty or does not belong to this machine Use a valid card 0x07 FileError File error At least one data record on the card is invalid and cannot be read The file is not safe security Card is faulty or does not belong to this ma...

Страница 12: ...rror Code Voltage is too high or too low Voltage monitoring at the outputs reports an error Ì The output voltage is too high Ì The output voltage is too low Select operating mode again or restart via NET library 2 x Check connections Environment error 0x20 Enum EKSError Value EKS Error Code Supply voltage too high All off Select operating mode again or restart via NET library 3 x Check connections...

Страница 13: ...r Meaning green red Firmware update See Normal operation Firmware data are sent to the device during normal operation 5 Hz The firmware update is activated via a separate command The firmware update was successful Acknowledge flashing code by restart or separate command Restore factory settings The device has been reset to the factory settings A restart is required ...

Страница 14: ...ted residual ripple 5 24 15 SELV PELV V DC Current consumption 100 mA Switching current 50 mA The following applies to the approval acc to UL Operation only with UL class 2 power supply or equivalent measures Switching load acc to UL DC 24 V class 2 External fuse operating voltage UB 1 5 10 A Rated impulse withstand voltage Uimp 1 kV Rated conditional short circuit current 200 A Resilience to vibr...

Страница 15: ...n the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the int...

Страница 16: ...uctions Electronic Key System EKS2 16 translation of the original operating instructions 2546099 01 10 21 13 3 Dimension drawing for EKS2 74 Z 92 66 500 62 8 3 5 X1 X2 16 82 3 5 19 73 Z 2 1 32 75 84 ca 41 Socket strip ...

Страница 17: ...ns Ì Check for contamination No servicing is required Repairs to the device are only allowed to be made by the manufacturer NOTICE The year of manufacture can be seen in the lower right corner of the type label The current version number in the format V X X X can also be found on the device 15 Service If servicing is required please contact EUCHNER GmbH Co KG Kohlhammerstraße 16 70771 Leinfelden E...

Страница 18: ...www euchner com Edition 2546099 01 10 21 Title Operating Instructions Electronic Key System EKS2 translation of the original operating instructions Copyright EUCHNER GmbH Co KG 10 2021 Subject to technical modifications no responsibility is accept ed for the accuracy of this information ...

Отзывы: