background image

*931221-00*

931221-00

Notes:

Deadbolt till not function with this strike.

Check with factory for retro t applications.

1.

For lock or device preparation, see their directions.

2.

Prepare frame for strike (see other side).

3.

Wire strike (Figure 1). (Switches on 6211ALDS only.)

4.

Install insert for auxiliary bolt operation (Figure 2).

5.

Test strike: Apply solenoid power. Fail secure (FSE) lip unlocks.

Fail safe (FS) lip locks. Figure 1 shows status of switches.

6.

Install strike with two #12-24 screws. Make sure clearance

between latch bolt and strike lip is 1/32” (Figure 3). If not,

uninstall strike, adjust (Figure 4), and reinstall.

7.

If latch bolt does not extend far enough to actuate tripper,

install extension (Figure 5). (Tripper on 6211ALDS only.)

8.

Test door: With strike unlocked, door opens with latch bolt

extended. When door closes, latch bolt rides over strike lip.

89/336/EEC

Figure 1

DC input is

nonpolarized

NOTE

!

J1

P1

P1 J1A

P1A

SO-12 or SO-24

12 VDC

or

24 VDC

12 VAC     

SO-12     12 VDC

     or

24 VAC     

SO-24     24 VDC

{
{

Wiring

for DC

supply

Wiring

for AC

supply

Solenoid

Use crimp

connectors to

splice 

 wiring

to P1 leads

Figure 2

Fit hook on insert

into notch on

faceplate

Yellow solenoid wires: 12 VDC, 0.57 A

Black solenoid wires: 24 VDC, 0.29 A

(also shown on strike label)

SOLENOID POWER REQUIREMENTS

Use crimp connectors to

splice 

 wiring to P2

leads; insulate unused leads

Switches  shown  with  tripper

depressed, strike lip closed and locked

(switches and tripper on 6211ALDS only)

J2

Fail safe (FS)

J2

Fail secure (FSE)

S1

S2

1
2
3
4
5
6

S1

S2

1
2
3
4
5
6

Standard: 5 A, 30 VDC

Gold: 0.25 A, 30 VDC

SWITCH  RATINGS

}

P2

Red  (C)
Blue
Yellow
White  (C)
Gray
Violet

}

S1

(monitors

tripper)

S2

(monitors

strike lip)

J2 P2

Figure 4

To adjust strike, loosen screws

A, B,

 and 

C

 and move backbox

sideways as necessary

A

D

B

C

For more

adjustment,

move screw 

A

to hole 

D

Figure 3

Top view;

faceplate not

shown for clarity

1/32”

Latch bolt

Strike lip

Tripper

Figure 5

Extension

Alternate

insert

position

NOTE:

Static Strength Rating 1500 lb.

Dynamic Strength Rating 70ft.-lb.

Endurance Rating 250,000 c.

         

    

  

    

Electric Strike, Single Door Aluminum Frame Mortise or 

Cylindrical Application

6211AL/6211ALDS

Installation Instructions

© Allegion 2014

Printed in U.S.A.

931221-00 Rev. 01/14-c

Customer Service

1-877-671-7011

www.allegion.com/us

Отзывы: