9
2124662-03-05/18 (translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTP-L.-AS1
EN
6.2.
Guard locking on version CTP-L2
(Guard locking actuated by power-ON and released by spring force)
Important!
Use as guard locking for personnel protection is possible only in special cases, after strict assessment
of the accident risk (see EN ISO 14119:2013, section 5.7.1)!
Activating guard locking:
Apply auxiliary power to the solenoid and set AS-Interface output bit D0.
Releasing guard locking:
No auxiliary power at the solenoid and/or clear AS-Interface output bit D0.
The magnetically actuated guard locking operates in accordance with the open-circuit current principle. If the solenoid is
not controlled (D0=0) or if auxiliary power is switched off, guard locking is released and the guard can be opened directly!
If the solenoid is controlled via the ASi bus (D0=1) and auxiliary power is applied to the solenoid, the guard locking pin is
held in extended position and the guard is locked.
6.3.
Switching states
Guard closed and locked
Guard closed and not locked
Guard open
Programming
State
D0, D1
D2, D3
Monitor diagnostics
Dual-channel
conditionally depen-
dent
Guard closed and locked
Code sequence
Green
Guard closed and not locked
Half-se-
quence
00
Yellow flashing
Invalid state
(guard open, guard locking active)
00
Half-se-
quence
Red flashing
(monitoring of the invalid state)
Guard open
00
00
Red
Address 0 or communication disrupted
–
Gray
Dual-channel
independent
Guard closed and locked
Code sequence
Green
Guard closed and not locked
Half-se-
quence
00
Red
Invalid state
(guard open, guard locking active)
00
Half-se-
quence
Red
Guard open
00
00
Red
Address 0 or communication disrupted
–
Gray
Dual-channel
dependent
Synchronization time
infinite
∞
Guard closed and locked
Code sequence
Green if guard was previously open or yellow flashing
after startup if only the guard locking was open.
Guard closed and not locked
Half-se-
quence
00
Yellow flashing if guard was previously closed.
Red if guard was previously open.
Invalid state
(guard open, guard locking active)
00
Half-se-
quence
Yellow flashing if guard was previously closed.
Red if guard was previously open.
Guard open
00
00
Red
Address 0 or communication disrupted
–
Gray