9
2543028-02-01/21 (Translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTP-I.-AS
EN
7. Manual release
Some situations require the guard locking to be released manually (e.g. malfunctions or an emergency). A function test must
be performed after release.
More information on this topic can be found in the standard EN ISO 14119:2013, section 5.7.5.1. The device can feature
the following release functions:
7.1.
Auxiliary release and auxiliary key release
In the event of malfunctions, the guard locking can be released with the auxiliary release or the auxiliary key release irre-
spective of the state of the solenoid.
Open the guard and close it again after resetting the auxiliary release or auxiliary key release. The device will then operate
normally again.
Important!
Ì
The actuator must not be under tensile stress during manual release.
Ì
After use, reset the auxiliary release and screw in and seal the locking screw (e.g. with sealing
lacquer).
Ì
The auxiliary key release must not be used to lock the switch during servicing to prevent activation
of guard locking, for example.
Ì
Loss of the release function due to mounting errors or damage during mounting.
Ì
Check the release function every time after mounting.
Ì
Please observe the notes on any enclosed data sheets.
7.1.1. Actuating auxiliary release
1. Unscrew locking screw.
2. Using a screwdriver, turn the auxiliary release to in the direction of the arrow.
¨
Guard locking is released.
Auxiliary re-
lease
Locking screw