Operating Instructions
Transponder-Coded Safety Switch CTM-CBI-BP
22
(Translation of the original operating instructions) 2541786-01-10/20
11. System status tables
11.1. Guard lock monitoring activated
Operating mode
Actuator/door position
Safety outputs FO1A and
FO1B
Guar
d lock monitoring
output/bit OL
Door position monitoring output/bit OD
LED indicator
Output
State
ST
ATE (gr
een)
DIA (r
ed) and
diagnostic output/ bit OI
LOCK (yellow)
Normal operation
off
off
off
off
5 Hz
Power Up
closed
on
on
on
Normal operation, door closed and locked
closed
off
on
on
1 x
inverse
Normal operation, door closed and locked, safety
outputs not switched because:
- Preceding device in the switch chain is signaling “door
open” (only with series connection)
closed
off
off
on
1 x
inverse
Normal operation, door closed and
not
locked
open
off
off
off
1 x
Normal operation, door open
open
off
off
off
1 x
1 x
Normal operation, door open, ready for guard locking
Teach-in operation
(only unicode)
open
off
off
off
3 x
Device in teach-in standby
closed
off
X
on
1 Hz
Teach-in operation
X
off
X
off
Positive acknowledgment after completion of teach-in
operation
Fault display
X
off
off
X
1 x
or
1 x in-
verse
Fault in the teach-in operation
Actuator removed from the actuating range prior to
the end of the teach-in operation or disabled actuator
detected.
X
off
off
off
3 x
Read error
(e.g. actuator faulty)
X
off
X
X
4 x
Output fault
(e.g. short circuit, loss of switching ability)
X
off
X
X
5 x
Environment errors
(e.g. operating voltage or operating temperature too
high)
X
off
X
X
2 x
Solenoid control input fault
X
off
X
X
1 x
Plausibility errors
X
off
off
off
X
Internal error
X
off
X
X
1 x
inverse
1 x
inverse Locking element stuck
Key to symbols
LED not illuminated
LED illuminated
10 Hz (8 s)
LED flashes for 8 s at 10 Hz
3 x
LED flashes three times, and this is then repeated
LEDs flash alternately
X
Any state