10.12. Connection of a single CTP/CTA-BR (separate operation)
If a single CTP/CTA-BR is used, connect the device as shown in
. The monitoring outputs can be routed to a control
system.
The switches can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 s. The
RST input must be connected to 0 V if it is not used.
If there is an internal error (see chapter
13. System status table CTP/CTA-L1/2-BR on page 37
), the reset does not work.
WARNING
In the event of a fault, loss of the safety function due to incorrect connection.
Ì
To ensure safety, both safety outputs FO1A and FO1B must always be evaluated.
Important!
Ì
The example shows only an excerpt that is relevant for connection of the CTP/CTA system.
The example illustrated here does not show complete system planning. The user is responsi-
ble for safe integration into the overall system. Detailed application examples can be found at
www.euchner.com. Simply enter the order number of your switch in the search box. You will find all
available connection examples for the device in
Downloads
.
Safety outputs
Door monitoring
Safety inputs
Read head
Actuato
r
Monitoring outputs
X2:5
NC
X2:3
OI
Diagnostics
Guardlocking
active
FI1A
X1:6
FI1B
X1:1
-B1
UB
X1:2
IMP
X2:4
X2:1
IMM
RST
X1:8
X1:7
0V UB
X2:2
OD
X1:3
FO1A
X1:4
FO1B
X1:5
OL
CTP
24V DC
0V
Connected load
1
2
-F1
1
2
-F2
0V
/
24V
/
Figure 4:
Connection example for separate operation, version with plug connectors 2xM12