2110788-13-03/20 (Translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CET.-AR-…
EN
10.1. Notes about
Important!
Ì
This device is intended to be used with a
Class 2
power source in accordance with UL1310.
As an alternative an LV/C (Limited Voltage/Current) power source with the following properties can
be used:
- This device shall be used with a suitable isolating source in conjunction with a fuse in accordance
with UL248. The fuse shall be rated max. 3.3 A and be installed in the max. 30 V DC power supply
to the device in order to limit the available current to comply with the
requirements. Please note
possibly lower connection ratings for your device (refer to the technical data).
Ì
For use and applications as per the
requirements
1)
, a connecting cable listed under UL cate-
gory code CYJV/7 must be used.
1) Note on the scope of the UL approval: the devices have been tested as per the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock
and fire).
10.2. Safety in case of faults
Ì
The operating voltage U
B
and the solenoid voltage U
CM
are reverse polarity protected.
Ì
The safety outputs OA/OB are short circuit-proof.
Ì
A short circuit between OA and OB is detected by the switch.
Ì
A short circuit in the cable can be excluded by laying the cable with protection.
10.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of switches and current required for the
outputs. The following rules apply:
Max. current consumption of an individual switch I
max
I
max
= I
UB
+ I
OUT
+ I
OA
+
OB
(+ I
OUT D
*)
I
UB
= Switch operating current (80 mA)
I
OUT
/ I
OUT D
= Load current of monitoring outputs (2 x max. 50 mA)
I
OA+OB
= Load current of safety outputs OA + OB (2 x max. 200 mA)
* only for version with door monitoring output
Max. current consumption of a switch chain
Σ
I
max
Σ
I
max
= I
OA+OB
+ n x (I
UB
+ I
OUT
(+ I
OUT D
*))
n = Number of connected switches
* only for version with door monitoring output