Operating Instructions
Transponder-Coded Safety Switch CTP/CTA-L1/2-BP
20
(translation of the original operating instructions) 2537377-01-05/21
5.7.
Connection
The device is connected as shown in
. The monitoring outputs can be routed to a control system.
The switch can be reset via the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 s. The RST
input must be connected to 0 V if it is not used.
If there is an internal error (see chapter
5. System status table CTP/CTA-L1/2-BP on page 26
), the reset does not work.
WARNING
In the event of a fault, loss of the safety function due to incorrect connection.
Ì
To ensure safety, both safety outputs FO1A and FO1B must always be evaluated.
Important!
Ì
The example shows only an excerpt that is relevant for connection of the CTP/CTA system.
The example illustrated here does not show complete system planning. The user is responsi-
ble for safe integration into the overall system. Detailed application examples can be found at
www.euchner.com. Simply enter the order number of your switch in the search box. You will find all
available connection examples for the device in
Downloads
.
Safety Outputs
Door
Monitoring
Monitoring Outputs
Read Head
Actuator
Diagnostic
-B1
UB
2
0 V
UB
7
OD
6
FO1A
3
FO1B
4
OI/C
5
IMP
1
IMM
8
Connected load
1
2
-F1
13
14
-S1
24V DC
0 V
24V DC
0 V
Fig. 3:
Connection example; version with plug connectors 2xM12