background image

  

PLB

Oil Furnaces

 – 

Furnace Manual

670-000-001/0204  

13

6

Wire furnace & burner

Electric shock hazard. Can cause severe personal injury or death if power source, including service switch on furnace, is not 
disconnected before installing or servicing. 

Wire burner 

The burner harness is factory-wired to the furnace at the factory. 
Plug the burner harness into the mating burner connector to wire the 
burner. Refer to the wiring diagram on pages 14, 15 and 16 for 
further information. 

Install and wire thermostat 

Locate the room thermostat on an interior wall in the natural 
circulating path of room air. Do not locate thermostat so it is exposed 
to cold air infiltration, drafts from windows or doors, air currents from 
supply or return air registers, behind obstructions, on a shelf, in a 
closet, or in a corner. 

Ensure the thermostat won’t be exposed to heat from nearby 
fireplace, radio, television, lamp or rays from the sun. Do not mount 
thermostat on a wall over a supply or return duct, chimney or vent. 

Connect power wiring 

All wiring must conform to : 

x

National Electrical Code, ANSI/NFPA 70, latest edition and any 
additional national, state or local codes. 

x

In Canada, CSA C22.1 Canadian Electrical Code Part One and 
any local codes. 

x

Wiring must be N.E.C. Class 1. If original wire as supplied with 
furnace must be replaced, type 105

o

 C wire or equivalent must 

be used. Supply wiring to furnace must be sized for the load 
required (see section 12). 

x

Provide electrical ground at furnace as required by codes. 

Connect 120 VAC/60 Hertz, single phase separate electrical line 
from the main house panel to the power leads in the external burner 
junction box as shown on wiring diagram, pages 14, 15 and 16. 
Provide a fused disconnect in the power wiring, following all local 
codes.

Ensure the wire size and type are adequate for the electrical load 
(see section 12 and furnace nameplate for value). 

Limit control 

The furnace is equipped with a fan switch/limit control. This control 
limits the air leaving the heat exchanger to 200

o

 F or less. The fan 

switch continues fan operation until the air drops to a preset 
temperature. For most installations, set the blower ON setting at 
110

o

 F and blower OFF setting at 90

o

 F. If a longer cool down period 

is desired, lower the OFF setting. 

WARNING 

Содержание PLB210 Low Boy

Страница 1: ...s furnace or any other appliance Ventilate house while operating furnace for the first time Odors may be emitted for a brief period Do not alter this furnace in any way The manufacturer will not be li...

Страница 2: ...e a mixture of gasoline and oil waste fuel refuse or any other substance in the burner of furnace Installation Do not block flow of combustion or ventilation air to furnace Do not block or obstruct th...

Страница 3: ...arances Provide no less than the minimum clearances given in Table 1 to ensure the furnace can be properly operated serviced and maintained Always apply whichever clearance is LARGER combustible const...

Страница 4: ...filtration from outside Each opening should be at least 140 sq in per 1 GPH input 1 sq in per 1000 BTU input of all fuel burning appliances plus requirements for any equipment that can pull air from r...

Страница 5: ...to avoid Spray cans containing chloro fluorocarbons Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used fo...

Страница 6: ...Provide ventilated thimble per all applicable codes where vent pipe passes through wall or ceiling Failure to comply could result in severe personal injury death or substantial property damage Duct l...

Страница 7: ...urnace installed with a 4 ton air conditioning evaporator coil Heating mode air flow is still 1 050 cfm Cooling mode air flow use Equation 3 4 CFM 4 x 400 1 600 cfm x The larger number is 1 600 cfm co...

Страница 8: ...8 7 7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15...

Страница 9: ...12 600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16...

Страница 10: ...injury or death The horizontal vent must slope upwards away from the furnace a minimum of inch per foot Connection must be made above bottom of chimney to avoid blockage Vent pipe must not enter chim...

Страница 11: ...Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Use only flare fittings Do not use compression fittings Failure to comply could result in severe personal injury death o...

Страница 12: ...PLB Oil Furnaces Furnace Manual 12 670 000 001 0204 Notes...

Страница 13: ...rm to x National Electrical Code ANSI NFPA 70 latest edition and any additional national state or local codes x In Canada CSA C22 1 Canadian Electrical Code Part One and any local codes x Wiring must...

Страница 14: ...PLB Oil Furnaces Furnace Manual 14 670 000 001 0204 6 Wire furnace burner continued Figure 1 Wiring PLB furnace with direct drive blower DNS 0913 Rev A...

Страница 15: ...PLB Oil Furnaces Furnace Manual 670 000 001 0204 15 6 Wire furnace burner continued Figure 2 Wiring PLB furnaces with direct drive blower DNS 0914 Rev B...

Страница 16: ...PLB Oil Furnaces Furnace Manual 16 670 000 001 0204 6 Wire furnace burner continued Figure 3 Wiring PLB furnaces with direct drive blower DNS 0873 Rev B...

Страница 17: ...ber CO2 between 10 and 11 with 0 smoke To start furnace continued Make final burner adjustments using combustion test equipment to assure proper operation 8 Check furnace and duct system for proper op...

Страница 18: ...ossible flue gas leakage and carbon monoxide emissions leading to severe personal injury or death 24 Limit control tested per To start up in this manual 25 Furnace cycled with thermostat Raise to high...

Страница 19: ...ozzle and electrode position Check ignition transformer output Reference burner manufacturers instructions Check tube insertion and alignment Check nozzle and electrode position Reference burner manuf...

Страница 20: ...G WARNING Consult with homeowner to see if there were any Check sequence of operation problems with furnace or system during the prior Check flame characteristics heating season or cooling season Perf...

Страница 21: ...x Do not attempt to start burner when excess oil has accumulated when unit is full or vapor or when combustion chamber is very hot x Do not start burner unless collector box vent and burner mounting d...

Страница 22: ...PLB Oil Furnaces Furnace Manual 22 670 000 001 0204 11 Components and replacement parts Figure 4 Model PLB 210 furnaces Component locations DNS 0879 Rev B...

Страница 23: ...t 12 Front panel insulation B02756 3 4 HP direct drive motor 13 Gasket observation door B01014 w ith motor support 14 Channel w ire B01763 Blow er GT12 10 15 Floor B01769 01 item 35B housing included...

Страница 24: ...0 WC 168 000 138 000 1 20 82 6 GT12 10 3 4 Med High High 5 1950 1900 189 000 155 000 1 35 82 8 GT12 10 3 4 High High 5 2050 1900 210 000 171 000 1 50 81 9 GT12 10 3 4 High N A 5 2050 N A PLB 210 Insta...

Страница 25: ...0 210 000 1 50 1 25 70W 145 BECKETT BURNER Model AFG 3450 RPM Tube insertion 2 7 8 Input Model Firing rate USGPH Nozzle Delavan Head Low firing rate baffle Static disc PLB 210 Combustion air adjustmen...

Страница 26: ...om thermostat 2 If the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary...

Страница 27: ...PLB Oil Furnaces Furnace Manual X40101 Rev G...

Отзывы: