Electrical Test Instruments PI-2500-G2 and PI-5000-G2
Section V - Service Information and Documentation
==============================================================================
==============================================================================
Copyright(C) 1994-2021 Electrical Test Instruments, LLC. All Rights Reserved
Page IV-2
f)
When all parts are properly assembled, the bolt pattern should match
standard stabs
g)
Make sure selector switch is set to 2000
4.
Alternate 1000-amp output mode
a)
Connect series bars and stab adaptor assemblies per instructions for
2000-amp mode above.
b)
Connect a cable or bus bar between stab plates stamped #4 and #5.
c)
Connect cables for breaker testing to stab plates stamped #1 and #8
PRE-TEST INSTALLATION AND SET-UP (PI5000)
1.
The following components of the test set should be available and in good
condition:
a)
PI-2500 Main Unit
b)
AUX-5000 Auxiliary Unit
c)
Allen wrench (hex) to match socket head bolts
d)
Pneumatic or electric power ratchet
e)
Stab set or cables to match breaker to be tested
f)
Series bar (optional)
g)
Input power plugs and cables
h)
Input ground lead
i)
Auxiliary ground lead
j)
Contact lead set (If applicable)
k)
Remote initiate cable (optional)
2.
Remove any bus work or cables from the output bus terminals of the
PI2500
3.
Make sure selector switch on PI-2500 output end is set to 4000
4.
Make sure surfaces (especially on top) are clean and smooth.
5.
Install Vertical buss adaptors onto the PI-2500.
6.
Position the PI2500 in optimal place for testing, and lock casters.
7.
Install 4 vertical buss bars onto the PI-5000
8.
Align the AUX5000 in-line with the PI-2500, and carefully roll it directly to-
ward the output bus connectors.