background image

Vertical Installation

Place the cells on the rack (or cabinet) and make sure that the 
spacing allows the accommodation of the inter-cell connectors 
(around 10mm). Most batteries have cells connected in a simple 
series arrangement, so the cells should be arranged to preserve the 
sequence: positive (+), negative (-), positive (+), negative (-) throughout 
the whole battery.

WARNING

NEVER LIFT CELLS BY THE TERMINAL POSTS. ALWAYS USE 
APPROPRIATED DEVICES (SUCH AS LIFTING STRAPS AND 
SUITABLE MECHANICAL LIFTING DEVICES) TO PREVENT 
INJURY TO PERSONAL OR DAMAGE TO THE CELLS. 

For batteries to be installed on multiple tiers, start by placing the cells 
on the lower tier on either side of the frame where the stand sections 
meet. Any unused stand spaces should be on the upper tier.

For batteries on stepped racks, leave any unused space on the back 
(top) step.

Where multiple racks are arranged end-to-end, adjust the position 
of the adjacent end cells to accommodate the flexible inter-rack 
connectors.

Take particular care to preserve the positive to negative sequence 
when using flexible inter-tier, inter-step or inter-rack connectors 
between rows of cells. Leave the main positive and negative terminals 
of the battery free for connection to the charging source.
Check cell alignment.
Prepare the inter-cell connectors by cleaning the contact surfaces 
with a soft clean cloth.

Fit the inter-cell and inter-tier connectors using approved, insulated 
bolts and nuts. Ensure all bolts, connectors and cell terminals are free 
from dust or debris before connecting. 

Use insulated wrenches to tighten the parts firmly together, with 
torque setting of 23 Nm (203 in lbs).
Pay special attention to avoid short-circuiting the cells with any of the 
battery hardware.

Check tightness and cleanliness.

Horizontal Installation

All Eternity Technology standby cells can be stored vertically and 
horizontally. 

All Eternity Technology Solar cells up to and including 1200Ah can be 
stored both vertically and horizontally. If you require larger Solar cells 
to be stored horizontally please contact Eternity Technologies. When 
storing horizontally ensure that the internal plates are vertical (to 
check this is the correct the positive and negative terminals should be 
above or below each other ie not on the same level as per the diagram 
below):

5. Charging

a) Commissioning Charge

Batteries lose charge while in transit or during storage. For this 
reason, a refresh charge should be given before putting the battery 
into service.

Recommended charge settings - at the ambient temperature range 
of 20 °C to 25 °C – are as follows:

12 hours at constant voltage of 2.35 Vpc at 20°C (68°F)
{Current limitation 1.5 x I10 Amps}   
temperature compensation;
0°C = 2,45 Vpc
10°C = 2,40
20°C = 2,35
30°C = 2,32
35°C = 2,30

b) Float Charge

To maintain the battery in fully charged condition during normal 
battery operation or, after a discharge, to recover 90% of nominal 
capacity within 20 hours, a recommended float charge has to be 
applied.

Recommended float voltage settings are as follows:

Constant voltage 2.25 Vpc at 20°C (68°F) ±1%
{Current limitation 2xI10 Amps}   

When all cells have been connected up check the terminal voltage, 
this should equal to the sum of all the individual cell voltages. If the 
total voltage is different to the calculated figure, some cells may have 
been reversed.

Connect the positive terminal of the battery to the positive terminal of 
the charger and the battery negative to the charger negative.

Number the cells by using a set of numbering stickers. It is common 
practice to number the cells beginning with #1 at the positive end of 
the battery and following the sequence of electrical connection of the 
cells, through to the negative end of the battery.

Before installing the cells, clean all parts. Remove the short circuit 
ABS protectors from the terminal posts and clean them with a soft 
clean cloth.

Before replacing old batteries ensure all electrical loads are switched 
off.

Battery Room - Points to Consider:

•  Ensure the floor is structurally capable of carrying the battery load
•  The floor should be resistant to Electrolyte (diluted sulphuric acid)
•  There should be no ignitable sources near to the cells
•  Ensure there are no unauthorised access points to the battery room
•  All rooms should have the correct fire-fighting equipment fitted in 
case of emergency.

Содержание OPzV Series

Страница 1: ...dby Solar Batteries are designed to be used as back up power to support users that need reliable service continuity in case of power blackouts and outages of the electricity distribution network They can also be used in off grid and hybrid installations Installation Operation and Maintenance Solar Batteries ET IOM005 0520 ...

Страница 2: ...nel Observe the following precautions at all times Observe the operating instructions work on the battery should be carried out by qualified personnel only Exposed metal parts of the battery carry a voltage and are electrically live with the risk of short circuits Avoid any electrostatic charge before starting work on the battery first discharge any possible electricity from yourself by touching a...

Страница 3: ... and performance 3 Delivery Unpacking and storage Unpack the batteries as soon as they are delivered Verify that the equipment has been delivered in good condition Any damage must be reported immediately to the carrier and the damaged items retained for inspection by the carrier s representative The details on the label should be read carefully and the following points to be observed Cell Type Cel...

Страница 4: ...ernity Technologies When storing horizontally ensure that the internal plates are vertical to check this is the correct the positive and negative terminals should be above or below each other ie not on the same level as per the diagram below 5 Charging a Commissioning Charge Batteries lose charge while in transit or during storage For this reason a refresh charge should be given before putting the...

Страница 5: ...age value requires a thermal compensation of 3 5mV cell C for temperature increases For temperature decreases in the cell the voltage should be increased by 3 5mV Cell C See graph below Failure to change these values will lead to capacity problems and reduction in operational life c Equalizing Boost charge 2 35 2 4V Chargers usually have two adjustable charging voltages one for the floating charge...

Страница 6: ...ifferent number of cycles 9 Hybrid Applications Eternity Technologies Solar OPzV batteries can be used in a hybrid system alongside a diesel generator where the batteries are used to decrease the run time of the generator Charging is critical in this application and the user must ensure that the charging time is sufficient to fully charge the battery between cycles Failure to do this will result i...

Страница 7: ...l battery float voltage the voltage on pilot cells and temperature Once a year Check and record individual cell voltages Perform a discharge test according to IEC 60896 21 standard until the battery shows signs of degradation and then every six months thereafter Keep a log book to record all maintenance and inspection operations which will be helpful to monitor long term changes of the battery con...

Страница 8: ...tytechnologies com The Eternity Technologies range is built using only the highest quality and most efficient production processes at our state of the art manufacturing centre in the UAE It is this innovation modern design criteria and industry leading machinery that allows Eternity Technologies to not only meet the needs of the global industrial market with increased reliability but define it for...

Отзывы: