4.0  Delivery and Storage 

Unpack the cells as soon as they are delivered. 

Verify that the equipment has been delivered in good condition. Any damage must be reported immediately to the 
carrier and the damaged items retained for inspection by the carrier’s representative. 

For cells supplied filled and charged, check that the acid level in all the cells is at the MAX level.  If necessary, fill 
them with dilute sulfuric acid with the correct specific gravity (see characteristics described under section 5). 

If the cells cannot be installed immediately, store them in a clean, cool, dry place. 

To avoid damage to containers and lids, do not expose the cells to direct sunlight. 

STORAGE TIME FOR FILLED AND CHARGED CELLS IS LIMITED.  IT IS ESSENTIAL THAT THEY 
ARE PLACED ON CHARGE NO MORE THAN 90 DAYS FROM THE DATE OF SHIPMENT.  AT 
HIGHER TEMPERATURE, THAT TIME IS REDUCED.  FAILURE TO OBSERVE THIS CONDITION MAY 
RESULT IN SIGNIFICANTLY REDUCED CAPACITY AND SERVICE LIFE OR PERMANENT DAMAGE 
TO THE CELLS, AND MAY VOID PRODUCT WARRANTY. 

If the cells are to be stored for more than 90 days, they should undergo a freshening charge carried out according 
to the instructions in section 8.0. 

Charge should be carried out with the shipping cases open, or the cells completely unpacked, and with adequate 
ventilation to disperse the gases formed while charging. 

If continuous charging is not possible, the battery should be given a freshening charge at least every 60 days until 
permanently installed and placed on float charge. 

If the battery is supplied in a dry-charged condition (without electrolyte), it can be stored for up to 3 years, 
provided that it is adequately protected against condensation and the effects of high humidity.  For filling and 
commissioning of dry-charged batteries, see instructions given under sections 5.1 and 8.1. 

5.0 Electrolyte 

The following table gives specific gravity data at 77°F (25°C) for fully charged (B)LSe cells with the electrolyte at 
the maximum level: 

Nominal 
Specific Gravity 
(kg/L) 

Specific Gravity 
Range 
(kg/L) 

Specific Gravity for 
Filling Dry Charged Cells 
(kg/L) 

1.240 

1.230 – 1.250 

1.230 

 
High quality electrolyte for standby lead-acid batteries (which is a solution of pure sulfuric acid diluted with distilled 
water to the correct concentration) is required for the first filling of dry charged cells. If the electrolyte has been 
supplied by Eternacell, store it in a safe place until required. 

If electrolyte is purchased locally, make certain its characteristics are in accordance with the following table: 

Impurity 

Electrolyte for first filling 
(mg/l) 

Electrolyte for refilling 
(mg/l) 

Copper 0,5 

0,5 

Heavy metals (As, Bi, Sn, Sb) 

Iron 30 

100 

Chlorine 5 200 
Total azote 

60 

60 

Organic substances 

50 

50 

Other impurities 

250 

800 

Содержание BLSe 12-100

Страница 1: ...LSe and BLSe range Operating Installation Maintenance Instructions...

Страница 2: ......

Страница 3: ...6 0 Battery Room 3 7 0 Installation 3 8 0 Charging 4 8 1 Initial Charge of Dry Cells 4 8 2 Filled and Charged Cells Freshening Charge 5 8 3 Charging in Service 6 9 0 Specific Gravity 7 10 0 Maintenanc...

Страница 4: ......

Страница 5: ...equipment such as rubber gloves and goggles If acid is spilled on the skin wash immediately with copious amounts of clean water then cover with dry gauze If acid comes into contact with the eyes flus...

Страница 6: ...with adequate ventilation to disperse the gases formed while charging If continuous charging is not possible the battery should be given a freshening charge at least every 60 days until permanently i...

Страница 7: ...n working within the range of 68 F 20 C to 77 F 25 C but will function at temperatures between 0 F 18 C and 125 F 52 C High temperatures increase the performance but reduce battery life while low temp...

Страница 8: ...it abrasive paper Do not use a wire brush and be especially careful not to break through the lead plating Apply a light coating of no oxide grease to the contact making areas of each connector This is...

Страница 9: ...ing interval to every hour and continue charging until specific gravity and voltage remain constant for two hours and each cell has reached a minimum of 2 6V If the charger does not allow the cells to...

Страница 10: ...harge or that the cells should be topped up For comparison of electrolyte specific gravity vs temperature please refer to section 9 0 8 3 2 Equalize Charge Chargers usually have two adjustable voltage...

Страница 11: ...quired safety precautions should perform battery maintenance For regular monitoring of the battery condition a pilot cell should be selected The pilot cell should be near the middle of the battery str...

Страница 12: ...of Eternacell B LSe batteries is minimized when floating at 2 23V cell at 77 F 25 C Consumption increases at higher temperatures and or higher float voltages Never allow the electrolyte level to fall...

Страница 13: ...2 8 3 28 6 132 8 178 2 4 39 4 LSe 1100 2 1096 10 8 8 3 28 6 145 7 201 8 5 42 4 LSe 1200 2 1200 10 8 8 3 28 6 155 2 210 5 5 34 4 LSe 1300 2 1272 10 8 8 3 28 6 164 7 218 8 5 23 4 LSe 1400 2 1376 10 8 8...

Страница 14: ......

Страница 15: ......

Страница 16: ...L13 15 IO 0310 3 Powdered Metals Drive North Haven CT 06473 Tel 203 985 2700 Fax 203 985 2739 www eternacellbatteries com...

Отзывы: