EternaCell BLSe 12-100 Скачать руководство пользователя страница 5

 

1.0 Introduction 

Standby batteries are generally used to support equipment that needs continuous, reliable service even when the 
grid supply has failed. 

To ensure optimum performance and longest life, lead-acid batteries require good maintenance practices.  In 
addition, basic electrical and chemical safety precautions must be taken to protect personnel and equipment. 

The scope of this document is to supply the necessary instructions to correctly store, handle, install, use and 
maintain Eternacell (B)LSe batteries. 

2.0 Recommendations 

Carefully read this entire manual upon receipt before installing or operating the battery. 

FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE INJURY TO PEOPLE AND 
DAMAGE TO EQUIPMENT OR THE BATTERY ITSELF. 

Keep this manual in close proximity to the battery and easily accessible to personnel working on or near the 
battery. 

3.0 Safety 

Rules 

When handled correctly, batteries are safe.  However, there are some basic precautions that must be observed at 
all times to protect personnel and the environment. 

Batteries produce explosive gasses. 

They contain diluted sulfuric acid (electrolyte) which is a corrosive substance.  When handling and working with 
electrolyte always use protective clothing and equipment such as rubber gloves and goggles.  If acid is spilled on 
the skin, wash immediately with copious amounts of clean water, then cover with dry gauze.  If acid comes into 
contact with the eyes, flush with clean water for at least 15 minutes.  In all cases, obtain immediate medical 
attention. 

Exposed metal parts of the battery always carry a voltage and are electrically live with the risk of short circuits. 

Avoid electrostatic discharge.  Before starting work on the battery, discharge any static electricity buildup.  
Wearing anti-static boots or wristbands is a good way to avoid static altogether. 

Always take the following precautions: 

 

Keep batteries upright. 

 

Use insulated tools. 

 

DO NOT place or drop metal objects on top of the battery. 

 

DO NOT wear watches, rings or other jewelry. Remove any articles of clothing with metal parts that might 
come in contact with the battery terminals. 

 

DO NOT smoke and DO NOT use open flames or create electric sparks. 

 

Make sure that first aid kits and fire extinguishers are easily accessible. 

 

Make sure that water facilities are available in case of accidental contact with acid occurs. 

 

Have neutralizing products easily accessible in case of spillage. 

 
Used batteries contain hazardous and recyclable materials.  They must not be 
disposed with normal waste.  Methods of return and recycling must conform to the 
federal, state and local regulations in operation at the site where battery is located. 

Содержание BLSe 12-100

Страница 1: ...LSe and BLSe range Operating Installation Maintenance Instructions...

Страница 2: ......

Страница 3: ...6 0 Battery Room 3 7 0 Installation 3 8 0 Charging 4 8 1 Initial Charge of Dry Cells 4 8 2 Filled and Charged Cells Freshening Charge 5 8 3 Charging in Service 6 9 0 Specific Gravity 7 10 0 Maintenanc...

Страница 4: ......

Страница 5: ...equipment such as rubber gloves and goggles If acid is spilled on the skin wash immediately with copious amounts of clean water then cover with dry gauze If acid comes into contact with the eyes flus...

Страница 6: ...with adequate ventilation to disperse the gases formed while charging If continuous charging is not possible the battery should be given a freshening charge at least every 60 days until permanently i...

Страница 7: ...n working within the range of 68 F 20 C to 77 F 25 C but will function at temperatures between 0 F 18 C and 125 F 52 C High temperatures increase the performance but reduce battery life while low temp...

Страница 8: ...it abrasive paper Do not use a wire brush and be especially careful not to break through the lead plating Apply a light coating of no oxide grease to the contact making areas of each connector This is...

Страница 9: ...ing interval to every hour and continue charging until specific gravity and voltage remain constant for two hours and each cell has reached a minimum of 2 6V If the charger does not allow the cells to...

Страница 10: ...harge or that the cells should be topped up For comparison of electrolyte specific gravity vs temperature please refer to section 9 0 8 3 2 Equalize Charge Chargers usually have two adjustable voltage...

Страница 11: ...quired safety precautions should perform battery maintenance For regular monitoring of the battery condition a pilot cell should be selected The pilot cell should be near the middle of the battery str...

Страница 12: ...of Eternacell B LSe batteries is minimized when floating at 2 23V cell at 77 F 25 C Consumption increases at higher temperatures and or higher float voltages Never allow the electrolyte level to fall...

Страница 13: ...2 8 3 28 6 132 8 178 2 4 39 4 LSe 1100 2 1096 10 8 8 3 28 6 145 7 201 8 5 42 4 LSe 1200 2 1200 10 8 8 3 28 6 155 2 210 5 5 34 4 LSe 1300 2 1272 10 8 8 3 28 6 164 7 218 8 5 23 4 LSe 1400 2 1376 10 8 8...

Страница 14: ......

Страница 15: ......

Страница 16: ...L13 15 IO 0310 3 Powdered Metals Drive North Haven CT 06473 Tel 203 985 2700 Fax 203 985 2739 www eternacellbatteries com...