OPERATION CHECKS:

This product is fitted with an automatic, self-test 

function that will commission and test itself in 

accordance with the requirements of the British 

Standards.  Monthly and annual tests will be 

automatically completed as detailed below with 

tests including battery charge condition, functional 

test and duration test.

Monthly – ten minute functional test  

Annually – full three-hour duration test

•  On installation a date will be randomly assigned for 

the first monthly and first annual test.

•  The initial monthly test will be between 16 and 30 

days from installation.

•  The initial full-duration test will be between 200 

and 360 days from installation (annual tests will 

then be conducted every 360 days).

•  The schedule of these tests will be remembered 

for a period of 7 days if no power is supplied to the 

luminaire.

•  If there is a mains failure in 24 hours before a test 

is due to be conducted, the test will automatically 

be postponed until sufficient time is allowed to 

recharge the battery.

•  If there is a mains failure during the self-test 

operation the unit will go into emergency mode.

TESTING 

This product is designed to conduct self-testing in 

accordance with EN 62034, the results of monthly 

and annual tests should be endorsed on the test 

record form supplied.

Because of the possibility of a failure of the normal 

lighting supply occurring shortly after a period of 

testing of the emergency lighting system or during 

the subsequent recharge period, all full duration 

tests shall wherever possible be undertaken 

preceding time of low risk to allow for battery 

recharge.

 

Daily:

 

Visual inspection of the battery charge LED.

 

Each Month:

 

The product will be energised from its battery for 

adequate time to ensure that emergency mode is 

functioning correctly. 

 

Once Each Year:

 

The product will be placed into emergency mode 

and check that the duration provided meets the 

specified time period.

 

There is a control button within the fitting:

•  Press for 1 second to reset the timer function, the 

monthly test will then be conducted after 30 days 

and the annual test after 360 days.

•  Press for 3 seconds to initiate a 5 minute functional 

test.

NOTE:

 This can only be completed under mains 

conditions and accordingly must only be conducted 

by a qualified electrician.

PERFORMANCE AND FAULT INDICATORS:

Normal operation

constant green LED

Duration test underway

red indicator flashing rapidly

Battery circuit failure

red indicator flashing once every 3 seconds

Light source failure

red indicator flashing twice every 3 seconds

Failure of duration test

red indicator flashing three times every 3 seconds

Auto test function fails

red indicator flashing four times every 3 seconds

LED indicator off

in emergency mode (mains failure)