OPERATION CHECKS:
This product is fitted with an automatic, self-test
function that will commission and test itself in
accordance with the requirements of the British
Standards. Monthly and annual tests will be
automatically completed as detailed below with
tests including battery charge condition, functional
test and duration test.
Monthly – ten minute functional test
Annually – full three-hour duration test
• On installation a date will be randomly assigned for
the first monthly and first annual test.
• The initial monthly test will be between 16 and 30
days from installation.
• The initial full-duration test will be between 200
and 360 days from installation (annual tests will
then be conducted every 360 days).
• The schedule of these tests will be remembered
for a period of 7 days if no power is supplied to the
luminaire.
• If there is a mains failure in 24 hours before a test
is due to be conducted, the test will automatically
be postponed until sufficient time is allowed to
recharge the battery.
• If there is a mains failure during the self-test
operation the unit will go into emergency mode.
TESTING
This product is designed to conduct self-testing in
accordance with EN 62034, the results of monthly
and annual tests should be endorsed on the test
record form supplied.
Because of the possibility of a failure of the normal
lighting supply occurring shortly after a period of
testing of the emergency lighting system or during
the subsequent recharge period, all full duration
tests shall wherever possible be undertaken
preceding time of low risk to allow for battery
recharge.
Daily:
Visual inspection of the battery charge LED.
Each Month:
The product will be energised from its battery for
adequate time to ensure that emergency mode is
functioning correctly.
Once Each Year:
The product will be placed into emergency mode
and check that the duration provided meets the
specified time period.
There is a control button within the fitting:
• Press for 1 second to reset the timer function, the
monthly test will then be conducted after 30 days
and the annual test after 360 days.
• Press for 3 seconds to initiate a 5 minute functional
test.
NOTE:
This can only be completed under mains
conditions and accordingly must only be conducted
by a qualified electrician.
PERFORMANCE AND FAULT INDICATORS:
Normal operation
constant green LED
Duration test underway
red indicator flashing rapidly
Battery circuit failure
red indicator flashing once every 3 seconds
Light source failure
red indicator flashing twice every 3 seconds
Failure of duration test
red indicator flashing three times every 3 seconds
Auto test function fails
red indicator flashing four times every 3 seconds
LED indicator off
in emergency mode (mains failure)
SW1