ETC Installation Guide

0–10 V Dimming Switch Sensor

DIP Switch Settings

Set the DIP switches according to installation requirements. See

Modes on the

facing page

for each operation mode available on your switch sensor model.

Function

Setting

Switch

1

2

3

4

5

HFD Sensitivity

Maximum

On*

On*

High

On

Off

Medium

Off

On

Low

Off

Off

Sensor Operation

PIR and HFD

On*

HFD only

Off

Occupancy/Vacancy

Sensing†

Occupancy

On*

Vacancy

Off

Push Button Operation

Control‡

On/Off

On

Presentation

Mode

Off

*Default settings.

†See

Operation

for more information.

‡Determines button function according to the sensing mode selected (DIP switch 4).

0–10 V Dimming Switch Sensor

Page 8 of 12

ETC

Содержание Sohrana Dual Tech

Страница 1: ...two buttons to set the light level for the next occupancy action By factory default the sensor is configured as an occupancy sensor meaning that the sensor will turn on the lights when occupancy is d...

Страница 2: ...Dimming Switch Sensor Sensor Coverage Side view Top view 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft 6 m 20 ft 1 2 m 4 ft 6 m 20 ft 2 1 m 7 ft A Minor Motion B Major Motion 180 Detection B A 0 10 V Dimming...

Страница 3: ...cupant within the desired sense range should be able to clearly see the sensor line of sight The sensor is more sensitive to the movements crossing the detection zones than those moving toward or away...

Страница 4: ...te Sensor DIM Violet DIM Pink Note This equipment must be grounded for operation Maximum Load Ballast Electronic LED 500 W VA 120 VAC 800 W VA 277 VAC Environment Ambient temperature 10 C 55 C 14 F 13...

Страница 5: ...CTRIQUE Cette appareil utilise une haute tension et ne doit tre install que par un installateur qualifi ou un lectricien Suivez tous les codes locaux pour l installation Avant de raccorder le c blage...

Страница 6: ...ide ON 1 2 LUX TIME The sensor wires are pre stripped for convenience Prepare the installed wires and secure each connection type line dim dim load ground and neutral with a suitable wire nut not prov...

Страница 7: ...of its set level for 30 seconds when vacancy is detected after the delay time expires after which the sensor will turn off the load Customize the operation using the onboard DIP Switch Settings When...

Страница 8: ...n Setting Switch 1 2 3 4 5 HFD Sensitivity Maximum On On High On Off Medium Off On Low Off Off Sensor Operation PIR and HFD On HFD only Off Occupancy Vacancy Sensing Occupancy On Vacancy Off Push Butt...

Страница 9: ...Mode pressing the button turns off the connected lighting load immediately and will ignore any occupancy detection Pressing the button again turns on the lighting load and the sensor resumes normal o...

Страница 10: ...which sets the timer to 10 seconds Lux The Lux setting determines the ambient light level threshold when the sensor will inhibit switching on the lighting load If the light level is at or above the se...

Страница 11: ...place the sensor in manual dimming mode While in dimming mode you can use the buttons in the following ways Press and hold the left button to lower the lighting level to the lowest level 20 The senso...

Страница 12: ...n 1 See Time on page 10 If the sensor has been reconfigured from its factory default operational settings see DIP Switch Settings the sensor will operate as expected in Test mode Test 1 Move around th...