Paradigm ACP Basic Navigation
20
Status / Error Messages Generated by the Paradigm ACP
Message Displayed
Description
Action
System OK
No errors exist
No action required for normal operation.
Emergency Active
Panic/Emergency bypass
operation is active
Occurs only when the Paradigm ACP is
installed in a host DRd enclosure.
The
programmed Emergency bypass look is
played. If load shedding is set to “On” all
loads not in emergency are shed. Also the
dimming setup, restore defaults, load
dimming configuration, and update
firmware menus will be locked out from
user intervention.
Dimming Firmware /
Mismatch Detected
Firmware version
mismatch between the
DRd enclosure and the
Paradigm ACP.
Occurs only when the Paradigm ACP is
installed in a host DRd enclosure.
This is
resolved through a firmware update
procedure.
Dimming Engine
Communication Failure!
The Paradigm ACP cannot
communicate with the DRd
dimming engine properly.
Occurs only when the Paradigm ACP is
installed in a host DRd enclosure.
The
error is clearable by correcting the failure
point.
ACP and DRd
Configuration Mismatch
Occurs when the dimming
configuration stored locally
on the Paradigm ACP does
not match the configuration
running within the DRd
dimming engine.
Occurs only when the Paradigm ACP is
installed in a host DRd enclosure.
The
menu locks out additional navigation and
requires you to confirm use of either the
dimming rack configuration or use of the
dimming configuration as stored on the
Paradigm ACP. Alternatively you can
select “Quick Rack Setup” to create a new
configuration.
AX12X ACP Position
Error
An error display warns you
when the Paradigm ACP is
installed in “Rack 2” of a
cross-bussed application.
Occurs only when the Paradigm ACP is
installed in a cross-bussed host DRd
enclosure.
This error cannot be cleared
except by correctly installing the AX12X
interconnect cable or by moving the
Paradigm ACP to the enclosure with the
interconnect cable end labeled “rack 1”.
Version Mismatch:
LightDesigner version used
to create/edit the arch
configuration is a different
version than the Paradigm
ACP software.
Either update the configuration version
via LightDesigner software or downgrade
the Paradigm ACP software version to
resolve this mismatch.
Unassigned Processor
Please Assign
Processor / IP settings
Each processor must be
configured as one of the 20
possible per system.
Assign processor identity from the face
panel UI by the processor’s name (e.g.
“Processor 1”, “1st Floor West”, etc.).
Internal Clock Error /
Low Battery
An error displays during
processor boot, indicating
the real timeclock backup
battery is low.
Contact ETC Technical Services.