background image

4

2. Tap the button to scroll through the selections. When the yellow LED is blinking, 

press and hold the side button until all the LEDs blink (about 5 seconds)

All three LED’s will blink on and off quickly for a second followed by a pause, then 
repeats. When the sensor receives a range confirmation telegram from the linked 
controller,  the  sensor  displays  the  signal  strength  status  for  2  seconds,  see  table 
below

.

LED - blinking

Signal Strength

Status

Green 

-41 to -70 dBm

Best

Yellow 

-70 to -80 dBm

Good

Red  

-80 to -95 dBm

Not ideal, try moving sensor closer 

None

No  linked  controllers  detected.  Move  sensor  closer  or  add  telegram 

repeating

The test will repeat every 10 seconds and run for a duration of 180 seconds. 

Error Codes

When a low battery state has been detected during normal operation, the battery 
status is blinked about once per minute. A single red blink indicates the last measured 
battery voltage is low.  A triple red blink indicates the battery voltage is critically low 
(less than 2.0V) and should be replaced immediately.
A stuck button will cause the red LED to blink ~ every 5 seconds.

Equipment Profiles

EEP: F6-04-01 

Keycard activation switch

Accessories

PTM365BP1W - Single  gang barrier plate for switches - UL and CSA certified 

 

PTM365BP2W  - Dual gang barrier plate for switches - UL and CSA certified

 

FCC Part 15.231 - Remote Control Transmitters

Devices equipped with 902 MHz radio:

 

Contains FCC ID: SZV-TCM515U

 

Contains IC: 5713A-TCM515U
The enclosed device complies with Part 15 of the FCC Rules. 

 

Operation  is  subject  to  the  following  two  conditions:                   

 

(I.)  this  device  may  not  cause  harmful  interference  and

 

(ii.)  this  device  must  accept  any  interference  received, 

including  interference  that  may  cause  undesired 

operation.

IC RSS-210

 

 

For more information on Echoflex Solutions, scan the QR code

:

Copyright 2019  Echoflex Solutions, Inc. Specifications subject to change without notice.

Echoflex Solutions

38924 Queens Way, Unit #1, Squamish, BC, V8B 0K8, Canada

  

n

  

+1 778-733-0111

echoflexsolutions.com

  

n

  

 8DC-5896-1.0

 

n

  

Document Part # 8188M21-5896-1 Rev A 

 

n

  

11/19

Содержание Echoflex Keycard Switch Station

Страница 1: ...n LED blink visible through the keycard plastic and a card inserted transmission to linked receivers The KSS is powered by a replaceable CR2032 coin cell battery and has an expected lifetime of 100 000 actuations over 10 years The station will indicate a low battery condition by blinking a red LED once upon any card insertion The keycard station is activated with an 85 60 x 53 98 mm 3 37 x 2 125 c...

Страница 2: ...ed and the last measured battery voltage is good The LED blink is visible through the keycard plastic ambient light may need to be dimmed to view i Note When a card is inserted and a single Red LED blinks it is an indication that the message was transmitted but the battery voltage is low less than 2 2V When the Red LED blinks 3 times on a card insertion the message was not transmitted and the batt...

Страница 3: ...conds The LED blink is visible through the keycard plastic ambient light may need to be dimmed to view the LED blinks Test mode times out after 180 seconds Test Menu Single red blink Reset Single yellow blink Range Confirmation Single green blink Reserved for future use Single green red blink Factory use only Single green yellow blink Factory use only Reset When reset a successful switch start up ...

Страница 4: ...ple red blink indicates the battery voltage is critically low less than 2 0V and should be replaced immediately A stuck button will cause the red LED to blink every 5 seconds Equipment Profiles EEP F6 04 01 Keycard activation switch Accessories PTM365BP1W Single gang barrier plate for switches UL and CSA certified PTM365BP2W Dual gang barrier plate for switches UL and CSA certified FCC Part 15 231...

Отзывы: