Overview

The ELED1 Fixture Controller provides wireless control of individual fixture or 
single zone lighting based on occupancy state, manual switch action, 
ambient light levels, and gateway commands. 

This document covers installation of the ELED1 LED Fixture Controller 
models. The 

Echoflex LED Fixture Controller ELED1(H) Configuration Guide

 

is available for download at 

echoflexsolutions.com

.

The package contents includes the controller, installation guide, and 
mounting strap (for ELED1-BUS model).

Prepare for Installation

Echoflex recommends paying special attention to the installation 
environment. 

• High density construction materials and large metal appliances or 

fixtures in the space may disrupt wireless reception.

• Mount the controller to an electrical junction box or a panel in a 

location and at a height where it is not subject to tampering by 
unauthorized personnel.

Supplies required to install the controller (not provided):

• Appropriately sized wire nuts
• Wire insulation
• Small cable ties
• Two 3/8 inch #8 metal screws (for surface mounting strap only)

Violet

ELED1-BUS

BUS

8189M2100

ELED1-BUN

Содержание Echoflex ELED1-BUN

Страница 1: ...tion of the ELED1 LED Fixture Controller models The Echoflex LED Fixture Controller ELED1 H Configuration Guide is available for download at echoflexsolutions com The package contents includes the controller installation guide and mounting strap for ELED1 BUS model Prepare for Installation Echoflex recommends paying special attention to the installation environment High density construction materi...

Страница 2: ...ock This device utilizes high voltage and should only be installed by a qualified installer or electrician Follow all local codes for installation Before terminating the AC power wiring verify that the main breaker is in the off position and follow the proper lockout tag out procedures per NFPA Standard 70E AVERTISSEMENT Risque de décharge électrique Cette appareil utilise une haute tension et ne ...

Страница 3: ...wire nuts on all connections and individually cap any bare wires except the orange antenna wire 5 Connect the gray and the violet wires to the driver or ballast s dimming interface optional 6 Replace the electrical box cover plate 7 Restore power to the circuit Install ELED1 with Mounting Strap Mount the controller to the exterior of a lighting fixture or appliance using the supplied mounting stra...

Страница 4: ...Fixtures Diagram 1 of 2 Note The Micro USB port is for factory use only Do not attach cables or accessories to this port Max Switching Load 11 5A 120 277 VAC 50 60 Hz Electronic Ballast or LED Driver LED Driver ELED1 Max Dimming Load 100 mA sinking Max Impulse Voltage 4000 V Internal Relay Type 1 C Dimming output is Class 1 circuit Independently Mounted Control for Panel Mount Surface Mount Antenn...

Страница 5: ... 0 10 V intensity control of a dimming ballast or LED driver The orange wire is an antenna Do not cut cap or connect this wire Use only UL approved wire when making connections to the controller see table below Connection Color Specification Load Red 14 AWG 600 V Neutral White 14 AWG 600 V Line Black 14 AWG 600 V Dimming 0 10 V Violet 18 AWG 600 V Dimming GND Gray 18 AWG 600 V Normal Hot Normal Ne...

Страница 6: ... commissioned state 1 Press the Clear button until the Power and Learn LEDs start blinking 2 Release the Clear button The Power LED blink codes indicate the type and count of devices linked at pre commissioning To reset to factory default state 1 Press and hold the Clear button until the Power and Learn LEDs start blinking and continue to hold for 15 seconds until the LEDs turn solid 2 Release the...

Страница 7: ...roller is in factory default state the Power LED remains solid On If the controller has one or more devices linked to it the Power LED repeats a code of blinks that represent the type and number of linked devices Long blinks type Short blinks count Blink Codes Description Power LED Learn LED Factory default On solid Off Switch es 1 long blink followed by short blinks counting switches Off Occupanc...

Страница 8: ...de Blink On solid Toggle Store link ID On 4 seconds On solid On 4 seconds Clear link ID Off 4 seconds On solid Off 4 seconds Factory default On solid One blink on power up On solid FCC Part 15 231 Contains FCC ID SZV STM300U This device complies with part 15 of the FCC rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must...