Echoflex Installation Guide

Light Sensor

Installation Environment

You can install the Light Sensor controller to a finished ceiling surface or soft
ceiling tile, or you can attach it to a round junction box or single-gang RACO
junction box. The controller operates in ambient temperatures of 0°C to
70°C, non-condensing humidity.

You can mount the Light Sensor head directly into the controller, to a 1/2”
conduit knockout, or into a soft ceiling tile using the provided thread
extender. Install the Light Sensor head outdoors only when you mount it into
a weatherproof enclosure. The sensor in this weatherproof installation
scenario operates in ambient temperatures of -25°C to 70°C (-13°F to 158°F).

Parts and Supplies

Parts and Supplies

Sensor head with

controller

(E-LS)

Light Sensor

head

(E-LSH)

Light Sensor

controller

(E-LSC)

Soft ceiling tile adapter

X

X

EchoConnect and ground wire

pigtails

X

X

Light Sensor head thread

extender

X

X

1 each nuts and washers 3/4"

and 1"

X

X

2 each screws 6-32 x 3/4" and 6-

32 x 1-3/4"

X

X

Blank Sensor head

X

X

Note:

Follow all local code requirements for terminating wire. Use

appropriately sized wire nuts (not provided) to secure each
termination.

Light Sensor

Page 3 of 12

Echoflex

Содержание echoflex Elaho E-LS

Страница 1: ...are available in three models E LS Light Sensor head with controller E LSC Light Sensor controller only E LSH Light Sensor head only Each controller supports up to two Light Sensor heads One head may...

Страница 2: ...additional 2 5 mm2 14 AWG wire for grounding when control wires are not installed in grounded metal conduit Note When using Category 5 or equivalent cable on the EchoConnect communication bus please n...

Страница 3: ...ensor head outdoors only when you mount it into a weatherproof enclosure The sensor in this weatherproof installation scenario operates in ambient temperatures of 25 C to 70 C 13 F to 158 F Parts and...

Страница 4: ...stall Sensor Heads Remotely optional on page 7 Note The EchoConnect pigtail is only required when the sensor and controller are installed in series with other sensors If you are not continuing the dat...

Страница 5: ...troller also known as remoting the Sensor head see Install Sensor Heads Remotely optional on page 7 and then return to these instructions If you are not remoting the Sensor head proceed to Step 4 4 Or...

Страница 6: ...re nut or other termination used wire nuts are not provided b Twist the data typically black EchoConnect wire the black lead from the EchoConnect pigtail and any continuing EchoConnect typically black...

Страница 7: ...data terminal b Terminate the incoming data typically black wire to the data terminal c Terminate the incoming ground typically green yellow wire to the labeled ground terminal Install Sensor Heads Re...

Страница 8: ...a At the controller strip 9 10 mm 5 8 in of insulation from the ends of each installed head wire b Using a small 3 35 mm 1 8 in flat blade or 1 Phillips screwdriver loosen the terminals on the Primar...

Страница 9: ...on on page 11 DIP Switch 2 DIP switch 2 enables Custom Config which instructs the sensor to use settings that are configured using the ElahoAccess Mobile App This setting is Off by default When Custom...

Страница 10: ...ount The controller includes an LED labeled Mode Sensor Count that blinks green according to the number of Sensor heads connected to the controller Check this LED to ensure that the system has been wi...

Страница 11: ...ith the slots on the mounting plate and then twist clockwise until the two are locked into place Record Target Auxiliary button Record target button The Record Target button takes a snapshot of the cu...

Страница 12: ...high measured light threshold is Target Target x Deadband 100 To ensure a smooth transition the Dimming operation does not exceed a fade rate greater than one second per percent dimmed Switched Photo...

Отзывы: