ETC E-OCC Скачать руководство пользователя страница 9

Echoflex Installation Guide

Occupancy Sensor

Power Up

All EchoConnect terminations in the system must be made before applying
power to the system and sensor. When the sensor is powered up, the PIR LED
illuminates for one minute for calibration and warm-up. The PIR detection
features of the sensor will automatically adjust the sensitivity threshold to
eliminate nuisance tripping. During this time configuration is not allowed
and no events are triggered.

Configuration

Basic

A sensor that is set for Basic configuration mode (DIP switch 2 set to Off) can
be further configured locally using the other available DIP switch settings, and
the [MODE] and Auxiliary [A] buttons and their associated LEDs. See

Preset

below

.

Custom

A sensor that is set for Custom configuration mode (DIP switch 2 set to On)
can be customized using the ElahoAccess App.

For more detailed information about custom configuration options available
using ElahoAccess, see the ElahoAccess App integrated help system.

Preset

While in Basic configuration mode (DIP switch 2 set to Off), use the [MODE]
and Auxiliary [A] buttons to program the preset that is activated with an
occupancy detected state change. By default, this is Preset 1. When vacancy is
detected, the default action event is Off.

Follow these steps to configure the preset for your sensor:

1. Access the sensor electronics and press and hold the [MODE] button

for three seconds to enter “Program Mode.” The Mode LED lights in
amber to indicate the sensor is in Program Mode and the Auxiliary LED
flashes to indicate the preset number controlled by the occupancy
action. By default, this is Preset 1, therefore the LED will flash one time,
pause two seconds and flash again.

2. Press and release the Auxiliary [A] button the number of times that

corresponds to the preset that you want to use. For example, press the
[A] button eight times to set Preset 8. The LED flashes the number of
the preset used.

3. Press and release the [MODE] button to save the current setting.

Occupancy Sensor

Page 9 of 12

Echoflex

Содержание E-OCC

Страница 1: ...Occupancy Sensor provides 360 degree coverage of the installed location and is available in these models Model Coverage m 2 Coverage ft 2 E OCC SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m...

Страница 2: ...ht feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or adjacent rooms If the instal...

Страница 3: ...t is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the proper termination...

Страница 4: ...Connect pigtail as well as any continuing data EchoConnect wire together and secure with a wire nut c Repeat the above step for the data EchoConnect wire typically white and for the ESD ground wire ty...

Страница 5: ...ensor in series with other sensors or stations continuing the data run use the provided EchoConnect and ESD ground wire pigtails Termination connectors are not provided If you are not continuing the d...

Страница 6: ...and then bend each tine over in opposite directions for a secure fit on the unfinished side of the ceiling tile 5 Terminate EchoConnect and ESD ground wires to the terminal block on the sensor control...

Страница 7: ...d into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches on the sensor electronics provide for Space...

Страница 8: ...ation on page 9 When Custom Config is set to On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4...

Страница 9: ...available using ElahoAccess see the ElahoAccess App integrated help system Preset While in Basic configuration mode DIP switch 2 set to Off use the MODE and Auxiliary A buttons to program the preset t...

Страница 10: ...ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a...

Страница 11: ...tened to ten seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If aco...

Страница 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Отзывы: