Echoflex Installation Guide

Occupancy Sensor

Settings

The Elaho Responsive
Occupancy Sensor
participates in an Elaho
control system using the
configured Space and
Address, which are selectable
using the rotary switches on
the sensor electronics.

DIP switches and the
[MODE] button, also located
on the sensor electronics, set
the sensor functionality and
the occupancy detection
action when set to Basic
configuration mode. See

Configuration on page 9

.

Note:

When the sensor is placed into Custom configuration mode,

DIP switch 2 set to On, all other DIP switch and Mode button settings
are ignored.

Set Space and Address

Two rotary switches on the sensor electronics provide for Space and Address
assignment for the sensor. By default, these switches are set to Space 1,
Address 1. Commands are shared by all devices within a given space.

1. Set the Space rotary switch to the desired number (1 through 16) for

the space you want the sensor to control.

2. Set the Address rotary switch to desired address (1 through 16) for the

sensor identification in the selected space.

Note:

Do not duplicate a device Address within the same Space.

Occupancy Sensor

Page 7 of 12

Echoflex

Содержание E-OCC

Страница 1: ...Occupancy Sensor provides 360 degree coverage of the installed location and is available in these models Model Coverage m 2 Coverage ft 2 E OCC SR Small Room 41 8 m 2 at 2 4 m 450 ft 2 at 8 ft 74 3 m...

Страница 2: ...ht feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or adjacent rooms If the instal...

Страница 3: ...t is provided with the Cat5 Termination Kit 8186A1207 for information to terminate Cat5 wiring Not all topologies are supported using Cat5 careful planning is required to ensure the proper termination...

Страница 4: ...Connect pigtail as well as any continuing data EchoConnect wire together and secure with a wire nut c Repeat the above step for the data EchoConnect wire typically white and for the ESD ground wire ty...

Страница 5: ...ensor in series with other sensors or stations continuing the data run use the provided EchoConnect and ESD ground wire pigtails Termination connectors are not provided If you are not continuing the d...

Страница 6: ...and then bend each tine over in opposite directions for a secure fit on the unfinished side of the ceiling tile 5 Terminate EchoConnect and ESD ground wires to the terminal block on the sensor control...

Страница 7: ...d into Custom configuration mode DIP switch 2 set to On all other DIP switch and Mode button settings are ignored Set Space and Address Two rotary switches on the sensor electronics provide for Space...

Страница 8: ...ation on page 9 When Custom Config is set to On all other local DIP switch settings are ignored Instead the settings made by the ElahoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4...

Страница 9: ...available using ElahoAccess see the ElahoAccess App integrated help system Preset While in Basic configuration mode DIP switch 2 set to Off use the MODE and Auxiliary A buttons to program the preset t...

Страница 10: ...ends the grace period begins When the sensor detects vacancy the vacancy timeout period begins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a...

Страница 11: ...tened to ten seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If aco...

Страница 12: ...10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6 1 m 20 ft 6 1 m 20 ft 9 1 m 30 ft 9 1 m 30 ft 12 2 m 40 ft 12 2 m 40 ft High Ceiling...

Отзывы: